Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Arizona State University |
---|---|
Assessment Year | 2000 |
Principal Product | Evaporative Coolers |
NAICS | n/a |
SIC | 3585 - Refrigeration And Heating Equipment |
Sales | $10,000,000-$50,000,000 |
# of Employees | 125 |
Plant Area (Sq.Ft.) | 200,000 |
Annual Production | 65,000 Pieces |
Production Hrs. Annual | 2,100 |
Location (State) | AZ |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $128,285 | 2,002,638 | kWh | $0.06 |
Electricity Demand | $22,664 | 8,482 | kW-months/year | $2.67 |
Electricity Fees | $12,995 | - | $ | - |
Natural Gas | $111,937 | 17,238 | MMBtu | $6.49 |
TOTAL ENERGY COSTS | $297,443 | |||
RECOMMENDED SAVINGS* | $30,005 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $16,872 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Personnel Changes | Administrative Changes | Ancillary Material Cost | By-product Production | Electricity Usage | Electricity Demand | Personnel Changes | Administrative Changes | Ancillary Material Cost | By-product Production | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | $ | $ | $ | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7133 USE SEPARATE SWITCHES ON PERIMETER LIGHTING WHICH MAY BE TURNED OFF WHEN NATURAL LIGHT IS AVAILABLE |
Savings: $1,637 Cost: $1,266 |
$1,637 | 29,015 | - | - | - | - | - | - | - | - | - | - |
$1,637 29,015 kWh |
- - kW-months/year |
- - $ |
- - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $708 Cost: $607 |
$433 | 7,620 | $53 | 9 | $122 | - | - | - | $100 | - | - | - |
$433 7,620 kWh |
$53 9 kW-months/year |
$122 - $ |
- - $ |
$100 - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7261 INSTALL TIMERS AND/OR THERMOSTATS |
Savings: $591 Cost: $600 |
$591 | 10,551 | - | - | - | - | - | - | - | - | - | - |
$591 10,551 kWh |
- - kW-months/year |
- - $ |
- - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4226 USE / PURCHASE OPTIMUM SIZED COMPRESSOR |
Savings: $10,502 Cost: $30,380 |
$6,594 | 116,940 | $3,908 | 668 | - | - | - | - | - | - | - | - |
$6,594 116,940 kWh |
$3,908 668 kW-months/year |
- - $ |
- - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.6125 KEEP EQUIPMENT CLEAN |
Savings: $3,601 Cost: $232 |
$2,261 | 40,152 | $1,340 | 229 | - | - | - | - | - | - | - | - |
$2,261 40,152 kWh |
$1,340 229 kW-months/year |
- - $ |
- - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 3.6192 USE A LESS EXPENSIVE METHOD OF WASTE REMOVAL |
Savings: $795 Cost: $120 |
- | - | - | - | - | - | $795 | - | - | - | - | - |
- - kWh |
- - kW-months/year |
- - $ |
$795 - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 3.6192 USE A LESS EXPENSIVE METHOD OF WASTE REMOVAL |
Savings: $403 Cost: $60 |
- | - | - | - | - | - | $403 | - | - | - | - | - |
- - kWh |
- - kW-months/year |
- - $ |
$403 - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 4.812 APPLY FOR INVESTMENT INCENTIVES |
Savings: $1,640 Cost: $60 |
- | - | - | - | - | - | $1,640 | - | - | - | - | - |
- - kWh |
- - kW-months/year |
- - $ |
$1,640 - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 3.5316 CONTRACT A WOOD PALLET RECYCLING COMPANY |
Savings: $10,128 Cost: $120 |
- | - | - | - | - | - | - | - | - | - | $10,128 | - |
- - kWh |
- - kW-months/year |
- - $ |
- - $ |
- - $ |
$10,128 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $30,005 Cost: $33,445 |
$11,516 | 204,278 | $5,301 | 906 | $122 | - | $2,838 | - | $100 | - | $10,128 | - | $11,516 204,278 kWh |
$5,301 906 kW-months/year |
$122 - $ |
$2,838 - $ |
$100 - $ |
$10,128 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $16,872 Cost: $1,139 |
$2,694 | 47,772 | $1,393 | 238 | $122 | - | $2,435 | - | $100 | - | $10,128 | - | $2,694 47,772 kWh |
$1,393 238 kW-months/year |
$122 - $ |
$2,435 - $ |
$100 - $ |
$10,128 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | $ | $ | $ | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Personnel Changes | Administrative Changes | Ancillary Material Cost | By-product Production | Electricity Usage | Electricity Demand | Personnel Changes | Administrative Changes | Ancillary Material Cost | By-product Production |