Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Arizona State University |
---|---|
Assessment Year | 2005 |
Principal Product | gypsum board products |
NAICS | 327420 - Gypsum Product Manufacturing |
SIC | 3275 - Gypsum Products |
Sales | $100,000,000-$500,000,000 |
# of Employees | 130 |
Plant Area (Sq.Ft.) | 600,000 |
Annual Production | 1,300,000 Thousand Feet |
Production Hrs. Annual | 6,616 |
Location (State) | NV |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $869,735 | 17,642,832 | kWh | $0.05 |
Electricity Demand | $107,159 | 27,816 | kW-months/year | $3.85 |
Natural Gas | $929,178 | 96,737 | MMBtu | $9.61 |
TOTAL ENERGY COSTS | $1,906,072 | |||
RECOMMENDED SAVINGS* | $520,926 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | - |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Electricity Usage | Electricity Demand | Natural Gas | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $393,520 Cost: $200,000 |
- | - | - | - | $393,520 | 42,681 |
- - kWh |
- - kW-months/year |
$393,520 42,681 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4224 UPGRADE CONTROLS ON COMPRESSORS |
Savings: $46,489 Cost: $10,000 |
$42,036 | 854,396 | $4,453 | 1,157 | - | - |
$42,036 854,396 kWh |
$4,453 1,157 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $28,210 Cost: $1,000 |
$25,516 | 518,617 | $2,694 | 700 | - | - |
$25,516 518,617 kWh |
$2,694 700 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4226 USE / PURCHASE OPTIMUM SIZED COMPRESSOR |
Savings: $21,234 Cost: $10,000 |
$19,214 | 390,534 | $2,020 | 524 | - | - |
$19,214 390,534 kWh |
$2,020 524 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.2136 INSTALL / REPAIR INSULATION ON STEAM LINES |
Savings: $20,625 Cost: $11,478 |
- | - | - | - | $20,625 | 2,237 |
- - kWh |
- - kW-months/year |
$20,625 2,237 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $10,848 Cost: $1,000 |
$9,994 | 203,140 | $854 | 222 | - | - |
$9,994 203,140 kWh |
$854 222 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $520,926 Cost: $233,478 |
$96,760 | 1,966,687 | $10,021 | 2,603 | $414,145 | 44,918 | $96,760 1,966,687 kWh |
$10,021 2,603 kW-months/year |
$414,145 44,918 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: - Cost: - |
- | - | - | - | - | - | - - kWh |
- - kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Electricity Usage | Electricity Demand | Natural Gas |