IAC logo
IAC Assessment: AS0480
Sponsored by:
DOE MESC
IAC logo
IAC Assessment: AS0480
Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center Arizona State University
Assessment Year 2020
Principal Product Coated Paper Bags
NAICS 322220 - Paper Bag and Coated and Treated Paper Manufacturing
SIC 2673 - Bags: Plastics, Laminated, & Coated
Sales <$500,000
# of Employees 60
Plant Area (Sq.Ft.) 100,000
Annual Production 2,130,000,000 Pieces
Production Hrs. Annual 8,520
Location (State) AZ
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $270,802 4,745,859 kWh $0.06
Electricity Demand $59,151 7,609 kW-months/year $7.77
Electricity Fees $9,036 - $ -
TOTAL ENERGY COSTS $338,989
RECOMMENDED SAVINGS* $38,359 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $26,036
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Electricity Usage Electricity Demand
$ kWh $ kW-months/year
01: 2.4226 USE / PURCHASE OPTIMUM SIZED COMPRESSOR Savings:
$17,992
Cost:
$66,000
$15,210 266,842 $2,782 358 $15,210
266,842
kWh
$2,782
358
kW-months/year
02: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM Savings:
$10,276
Cost:
$9,045
$8,691 152,481 $1,585 204 $8,691
152,481
kWh
$1,585
204
kW-months/year
03: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$8,044
Cost:
$9,363
$6,747 118,368 $1,297 167 $6,747
118,368
kWh
$1,297
167
kW-months/year
04: 2.7232 REPLACE EXISTING HVAC UNIT WITH HIGH EFFICIENCY MODEL Savings:
$1,442
Cost:
$5,500
$968 16,994 $474 61 $968
16,994
kWh
$474
61
kW-months/year
05: 2.7135 INSTALL OCCUPANCY SENSORS Savings:
$605
Cost:
$2,300
$605 10,612 - - $605
10,612
kWh
-
-
kW-months/year
TOTAL RECOMMENDED Savings:
$38,359
Cost:
$92,208
$32,221 565,297 $6,138 790 $32,221
565,297
kWh
$6,138
790
kW-months/year
TOTAL IMPLEMENTED Savings:
$26,036
Cost:
$75,363
$21,957 385,210 $4,079 525 $21,957
385,210
kWh
$4,079
525
kW-months/year
Savings
Cost
$ kWh $ kW-months/year
Electricity Usage Electricity Demand Electricity Usage Electricity Demand