IAC Assessment: AS0494
Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center Arizona State University
Assessment Year 2020
Principal Product Treated Wastewater
NAICS 221320 - Sewage Treatment Facilities
SIC 4952 - Sewerage Systems
Sales <$500,000
# of Employees 10
Plant Area (Sq.Ft.) 50,000
Annual Production 1,348,000 Thousand Gallons
Production Hrs. Annual 8,760
Location (State) AZ
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $230,885 5,359,789 kWh $0.04
Electricity Demand $211,287 11,220 kW-months/year $18.83
Electricity Fees $38,193 - $ -
Natural Gas $64,089 10,914 MMBtu $5.87
TOTAL ENERGY COSTS $544,454
RECOMMENDED SAVINGS* $153,862 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $153,636
#|Description Savings
Cost
Status Electricity Usage Electricity Demand One-time Revenue or Avoided Cost Electricity Usage Electricity Demand One-time Revenue or Avoided Cost
$ kWh $ kW-months/year $ $
01: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM Savings:
$130,212
Cost:
$564
$49,706 1,155,948 $80,506 4,275 - - $49,706
1,155,948
kWh
$80,506
4,275
kW-months/year
-
-
$
02: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$12,021
Cost:
$31,867
$8,287 192,732 $4,935 262 $(-1,201) - $8,287
192,732
kWh
$4,935
262
kW-months/year
$(-1,201)
-
$
03: 2.6125 KEEP EQUIPMENT CLEAN Savings:
$3,890
Cost:
$2,174
$3,890 96,490 - - - - $3,890
96,490
kWh
-
-
kW-months/year
-
-
$
04: 2.7135 INSTALL OCCUPANCY SENSORS Savings:
$3,827
Cost:
$2,905
$3,827 89,005 - - - - $3,827
89,005
kWh
-
-
kW-months/year
-
-
$
05: 2.8112 COMBINE UTILITY METERS Savings:
$3,107
Cost:
$1,473
$(-8,921) - $9,849 - $2,179 - $(-8,921)
-
kWh
$9,849
-
kW-months/year
$2,179
-
$
06: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS Savings:
$518
Cost:
$382
$337 7,840 $181 10 - - $337
7,840
kWh
$181
10
kW-months/year
-
-
$
07: 2.6211 CONSERVE ENERGY BY EFFICIENT USE OF VENDING MACHINES Savings:
$226
Cost:
$354
$139 3,229 $87 5 - - $139
3,229
kWh
$87
5
kW-months/year
-
-
$
08: 2.7272 INSTALL HEAT PIPES / RAISE COOLING SETPOINT Savings:
$61
Cost:
$47
$38 891 $23 1 - - $38
891
kWh
$23
1
kW-months/year
-
-
$
TOTAL RECOMMENDED Savings:
$153,862
Cost:
$39,766
$57,303 1,546,135 $95,581 4,553 $978 - $57,303
1,546,135
kWh
$95,581
4,553
kW-months/year
$978
-
$
TOTAL IMPLEMENTED Savings:
$153,636
Cost:
$39,412
$57,164 1,542,906 $95,494 4,548 $978 - $57,164
1,542,906
kWh
$95,494
4,548
kW-months/year
$978
-
$
Savings
Cost
$ kWh $ kW-months/year $ $
Electricity Usage Electricity Demand One-time Revenue or Avoided Cost Electricity Usage Electricity Demand One-time Revenue or Avoided Cost