Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Arizona State University |
---|---|
Assessment Year | 2024 |
Principal Product | Education |
NAICS | 611110 - Elementary and Secondary Schools |
SIC | 8211 - Elementary And Secondary Schools |
Sales | <$500,000 |
# of Employees | 120 |
Plant Area (Sq.Ft.) | 1,001,856 |
Annual Production | 1 Units |
Production Hrs. Annual | 2,550 |
Location (State) | AZ |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $177,622 | 1,235,661 | kWh | $0.14 |
Electricity Demand | $30,640 | 3,833 | kW-months/year | $7.99 |
Electricity Fees | $26,970 | - | $ | - |
Natural Gas | $20,345 | 2,810 | MMBtu | $7.24 |
TOTAL ENERGY COSTS | $255,577 | |||
RECOMMENDED SAVINGS* | $111,504 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | - |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Fees | Ancillary Material Cost | Electricity Usage | Electricity Demand | Electricity Fees | Ancillary Material Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.8112 COMBINE UTILITY METERS |
Savings: $30,741 Cost: $605 |
$28,692 | - | $(-3,189) | - | $5,238 | - | - | - |
$28,692 - kWh |
$(-3,189) - kW-months/year |
$5,238 - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.9114 USE SOLAR HEAT TO MAKE ELECTRICTY |
Savings: $23,057 Cost: $176,288 |
$20,787 | 185,595 | $2,270 | 202 | - | - | - | - |
$20,787 185,595 kWh |
$2,270 202 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.9114 USE SOLAR HEAT TO MAKE ELECTRICTY |
Savings: $17,501 Cost: $95,089 |
$17,055 | 93,866 | $446 | 106 | - | - | - | - |
$17,055 93,866 kWh |
$446 106 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7132 INSTALL TIMERS ON LIGHT SWITCHES IN LITTLE USED AREAS |
Savings: $13,232 Cost: $5,780 |
$13,232 | 94,194 | - | - | - | - | - | - |
$13,232 94,194 kWh |
- - kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.9114 USE SOLAR HEAT TO MAKE ELECTRICTY |
Savings: $10,418 Cost: $95,089 |
$9,738 | 92,833 | $680 | 60 | - | - | - | - |
$9,738 92,833 kWh |
$680 60 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $7,127 Cost: $21,892 |
$6,181 | 34,029 | $791 | 187 | - | - | $155 | - |
$6,181 34,029 kWh |
$791 187 kW-months/year |
- - $ |
$155 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7144 INSTALL SPECTRAL REFLECTORS / DELAMP |
Savings: $4,422 Cost: - |
$1,909 | 13,655 | $638 | 85 | - | - | $1,875 | - |
$1,909 13,655 kWh |
$638 85 kW-months/year |
- - $ |
$1,875 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7272 INSTALL HEAT PIPES / RAISE COOLING SETPOINT |
Savings: $3,680 Cost: $136 |
$3,345 | 18,408 | $335 | 79 | - | - | - | - |
$3,345 18,408 kWh |
$335 79 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $1,326 Cost: $2,077 |
$1,132 | 6,438 | $194 | 42 | - | - | - | - |
$1,132 6,438 kWh |
$194 42 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $111,504 Cost: $396,956 |
$102,071 | 539,018 | $2,165 | 761 | $5,238 | - | $2,030 | - | $102,071 539,018 kWh |
$2,165 761 kW-months/year |
$5,238 - $ |
$2,030 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: - Cost: - |
- | - | - | - | - | - | - | - | - - kWh |
- - kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Fees | Ancillary Material Cost | Electricity Usage | Electricity Demand | Electricity Fees | Ancillary Material Cost |