Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Boise State University |
---|---|
Assessment Year | 2012 |
Principal Product | Manufactured homes |
NAICS | 321991 - Manufactured Home (Mobile Home) Manufacturing |
SIC | 2452 - Prefabricated Wood Buildings |
Sales | $10,000,000-$50,000,000 |
# of Employees | 71 |
Plant Area (Sq.Ft.) | 146,600 |
Annual Production | 590 Pieces |
Production Hrs. Annual | 2,024 |
Location (State) | ID |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $28,251 | 905,844 | kWh | $0.03 |
Electricity Demand | $17,602 | 4,183 | kW-months/year | $4.21 |
Electricity Fees | $21,490 | - | $ | - |
Natural Gas | $65,565 | 9,312 | MMBtu | $7.04 |
TOTAL ENERGY COSTS | $132,909 | |||
RECOMMENDED SAVINGS* | $32,694 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $9,791 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes | Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $2,118 Cost: $296 |
$1,040 | 31,720 | $1,078 | 188 | - | - | - | - |
$1,040 31,720 kWh |
$1,078 188 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 3.7312 IMPLEMENT A REGULAR MAINTENANCE PROGRAM TO REDUCE EMISSIONS FROM LEAKY VALVES AND PIPE FITTINGS |
Savings: $1,528 Cost: $300 |
$1,253 | 38,256 | $1,301 | 227 | - | - | $(-1,026) | - |
$1,253 38,256 kWh |
$1,301 227 kW-months/year |
- - MMBtu |
$(-1,026) - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $4,856 Cost: $4,997 |
$2,384 | 72,783 | $2,473 | 432 | - | - | - | - |
$2,384 72,783 kWh |
$2,473 432 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $831 Cost: $1,497 |
$408 | 12,462 | $423 | 74 | - | - | - | - |
$408 12,462 kWh |
$423 74 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7133 USE SEPARATE SWITCHES ON PERIMETER LIGHTING WHICH MAY BE TURNED OFF WHEN NATURAL LIGHT IS AVAILABLE |
Savings: $458 Cost: $600 |
$225 | 6,861 | $233 | 41 | - | - | - | - |
$225 6,861 kWh |
$233 41 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7231 USE RADIANT HEATER FOR SPOT HEATING |
Savings: $1,478 Cost: $500 |
$(-319) | (-9,756) | $(-26) | (-5) | $1,823 | 259 | - | - |
$(-319) (-9,756) kWh |
$(-26) (-5) kW-months/year |
$1,823 259 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7261 INSTALL TIMERS AND/OR THERMOSTATS |
Savings: $10,488 Cost: $570 |
- | - | - | - | $10,488 | 1,491 | - | - |
- - kWh |
- - kW-months/year |
$10,488 1,491 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7491 INSULATE GLAZING, WALLS, CEILINGS, AND ROOFS |
Savings: $10,937 Cost: $39,850 |
- | - | - | - | $10,937 | 1,555 | - | - |
- - kWh |
- - kW-months/year |
$10,937 1,555 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $32,694 Cost: $48,610 |
$4,990 | 152,326 | $5,482 | 957 | $23,248 | 3,305 | $(-1,026) | - | $4,990 152,326 kWh |
$5,482 957 kW-months/year |
$23,248 3,305 MMBtu |
$(-1,026) - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $9,791 Cost: $7,690 |
$5,309 | 162,082 | $5,508 | 962 | - | - | $(-1,026) | - | $5,309 162,082 kWh |
$5,508 962 kW-months/year |
- - MMBtu |
$(-1,026) - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes | Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes |