Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Boise State University |
---|---|
Assessment Year | 2013 |
Principal Product | Milk, Sour Cream, Cottage Cheese |
NAICS | 311511 - Fluid Milk Manufacturing |
SIC | 2026 - Fluid Milk |
Sales | $50,000,000-$100,000,000 |
# of Employees | 130 |
Plant Area (Sq.Ft.) | 100,000 |
Annual Production | 39,000 Thousand Gallons |
Production Hrs. Annual | 8,760 |
Location (State) | ID |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $377,051 | 12,815,595 | kWh | $0.03 |
Electricity Demand | $108,161 | 25,023 | kW-months/year | $4.32 |
Electricity Fees | $77,479 | - | $ | - |
Natural Gas | $967,680 | 131,248 | MMBtu | $7.37 |
TOTAL ENERGY COSTS | $1,530,371 | |||
RECOMMENDED SAVINGS* | $772,484 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $11,127 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | By-product Production | Electricity Usage | Electricity Demand | Natural Gas | By-product Production | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS |
Savings: $1,591 Cost: $260 |
$1,591 | 51,415 | - | - | - | - | - | - |
$1,591 51,415 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE |
Savings: $1,495 Cost: $1,840 |
$1,495 | 48,320 | - | - | - | - | - | - |
$1,495 48,320 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT |
Savings: $1,533 Cost: $2,806 |
$(-59) | (-1,921) | - | - | $1,592 | 220 | - | - |
$(-59) (-1,921) kWh |
- - kW-months/year |
$1,592 220 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS |
Savings: $2,077 Cost: $689 |
$1,647 | 53,220 | $430 | 73 | - | - | - | - |
$1,647 53,220 kWh |
$430 73 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $2,037 Cost: $126 |
$2,037 | 65,843 | - | - | - | - | - | - |
$2,037 65,843 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.2136 INSTALL / REPAIR INSULATION ON STEAM LINES |
Savings: $5,422 Cost: $3,959 |
- | - | - | - | $5,422 | 749 | - | - |
- - kWh |
- - kW-months/year |
$5,422 749 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.2136 INSTALL / REPAIR INSULATION ON STEAM LINES |
Savings: $3,187 Cost: $1,066 |
- | - | - | - | $3,187 | 440 | - | - |
- - kWh |
- - kW-months/year |
$3,187 440 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7233 USE PROPERLY DESIGNED AND SIZED HVAC EQUIPMENT |
Savings: $11,756 Cost: $210 |
$11,756 | 379,946 | - | - | - | - | - | - |
$11,756 379,946 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.1336 INSTALL EQUIPMENT TO UTILIZE WASTE FUEL |
Savings: $743,387 Cost: $1,700,000 |
- | - | - | - | - | - | $743,387 | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
$743,387 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $772,484 Cost: $1,710,956 |
$18,467 | 596,823 | $430 | 73 | $10,201 | 1,409 | $743,387 | - | $18,467 596,823 kWh |
$430 73 kW-months/year |
$10,201 1,409 MMBtu |
$743,387 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $11,127 Cost: $5,034 |
$5,275 | 170,478 | $430 | 73 | $5,422 | 749 | - | - | $5,275 170,478 kWh |
$430 73 kW-months/year |
$5,422 749 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | By-product Production | Electricity Usage | Electricity Demand | Natural Gas | By-product Production |