IAC logo
IAC Assessment: CI0002
Sponsored by:
DOE MESC
IAC logo
IAC Assessment: CI0002
Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of California, Irvine
Assessment Year 2022
Principal Product Residential Door Locks and Cabinet Hardware Accessories
NAICS 332999 - All Other Miscellaneous Fabricated Metal Product Manufacturing
SIC 3429 - Hardware, Nec
Sales $100,000,000-$500,000,000
# of Employees 389
Plant Area (Sq.Ft.) 218,600
Annual Production 1,000,000 Pieces
Production Hrs. Annual 3,060
Location (State) CA
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $279,304 1,386,000 kWh $0.20
Natural Gas $15,033 1,397 MMBtu $10.76
LPG $38,508 1 MMBtu $38,508.00
TOTAL ENERGY COSTS $332,845
RECOMMENDED SAVINGS* $104,906 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* -
#|Description Savings
Cost
Status Electricity Usage LPG Personnel Changes Ancillary Material Cost Electricity Usage LPG Personnel Changes Ancillary Material Cost
$ kWh $ MMBtu $ $ $ $
01: 2.8227 ADJUST / MAINTAIN FORK LIFT TRUCKS FOR MOST EFFICIENT OPERATION Savings:
$33,479
Cost:
$80,000
- - $33,479 1 - - - - -
-
kWh
$33,479
1
MMBtu
-
-
$
-
-
$
02: 2.7491 INSULATE GLAZING, WALLS, CEILINGS, AND ROOFS Savings:
$27,300
Cost:
$24,600
$27,300 135,486 - - - - - - $27,300
135,486
kWh
-
-
MMBtu
-
-
$
-
-
$
03: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$18,201
Cost:
$1,800
$18,201 90,329 - - - - - - $18,201
90,329
kWh
-
-
MMBtu
-
-
$
-
-
$
04: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE Savings:
$12,649
Cost:
$30,000
$12,649 62,776 - - - - - - $12,649
62,776
kWh
-
-
MMBtu
-
-
$
-
-
$
05: 2.4325 UPGRADE CONVEYORS Savings:
$3,825
Cost:
$8,040
- - - - $3,825 - - - -
-
kWh
-
-
MMBtu
$3,825
-
$
-
-
$
06: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE Savings:
$3,680
Cost:
-
$3,680 18,262 - - - - - - $3,680
18,262
kWh
-
-
MMBtu
-
-
$
-
-
$
07: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$2,733
Cost:
$2,167
$2,733 13,563 - - - - - - $2,733
13,563
kWh
-
-
MMBtu
-
-
$
-
-
$
08: 2.7135 INSTALL OCCUPANCY SENSORS Savings:
$1,717
Cost:
$2,625
$1,717 8,520 - - - - - - $1,717
8,520
kWh
-
-
MMBtu
-
-
$
-
-
$
09: 2.7134 USE PHOTOCELL CONTROLS Savings:
$1,322
Cost:
$1,350
$1,152 5,718 - - $77 - $93 - $1,152
5,718
kWh
-
-
MMBtu
$77
-
$
$93
-
$
TOTAL RECOMMENDED Savings:
$104,906
Cost:
$150,582
$67,432 334,654 $33,479 1 $3,902 - $93 - $67,432
334,654
kWh
$33,479
1
MMBtu
$3,902
-
$
$93
-
$
TOTAL IMPLEMENTED Savings:
-
Cost:
-
- - - - - - - - -
-
kWh
-
-
MMBtu
-
-
$
-
-
$
Savings
Cost
$ kWh $ MMBtu $ $ $ $
Electricity Usage LPG Personnel Changes Ancillary Material Cost Electricity Usage LPG Personnel Changes Ancillary Material Cost