Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of California, Irvine |
---|---|
Assessment Year | 2022 |
Principal Product | Metal Finishing |
NAICS | 332813 - Electroplating, Plating, Polishing, Anodizing, and Coloring |
SIC | 3471 - Plating And Polishing |
Sales | $10,000,000-$50,000,000 |
# of Employees | 150 |
Plant Area (Sq.Ft.) | 170,000 |
Annual Production | 50,000 Pieces |
Production Hrs. Annual | 6,240 |
Location (State) | CA |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $924,829 | 7,545,402 | kWh | $0.12 |
Electricity Demand | $135,770 | 10,185 | kW-months/year | $13.33 |
Natural Gas | $514,322 | 58,422 | MMBtu | $8.80 |
LPG | $33,825 | 3,000 | MMBtu | $11.28 |
TOTAL ENERGY COSTS | $1,608,746 | |||
RECOMMENDED SAVINGS* | $112,736 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | - |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | LPG | Electricity Usage | Electricity Demand | Natural Gas | LPG | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | MMBtu | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7491 INSULATE GLAZING, WALLS, CEILINGS, AND ROOFS |
Savings: $28,328 Cost: $32,800 |
$28,328 | 231,104 | - | - | - | - | - | - |
$28,328 231,104 kWh |
- - kW-months/year |
- - MMBtu |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.8227 ADJUST / MAINTAIN FORK LIFT TRUCKS FOR MOST EFFICIENT OPERATION |
Savings: $26,391 Cost: $90,000 |
$(-7,434) | (-60,653) | - | - | - | - | $33,825 | 3,000 |
$(-7,434) (-60,653) kWh |
- - kW-months/year |
- - MMBtu |
$33,825 3,000 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT |
Savings: $22,728 Cost: $6,000 |
$16,330 | 133,230 | $6,398 | 480 | - | - | - | - |
$16,330 133,230 kWh |
$6,398 480 kW-months/year |
- - MMBtu |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.9114 USE SOLAR HEAT TO MAKE ELECTRICTY |
Savings: $14,859 Cost: $82,655 |
$7,469 | 60,938 | $7,390 | 554 | - | - | - | - |
$7,469 60,938 kWh |
$7,390 554 kW-months/year |
- - MMBtu |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.1224 REPLACE BOILER |
Savings: $13,563 Cost: $27,000 |
$(-25,698) | (-209,664) | $(-1,074) | (-81) | $40,335 | 4,582 | - | - |
$(-25,698) (-209,664) kWh |
$(-1,074) (-81) kW-months/year |
$40,335 4,582 MMBtu |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE |
Savings: $4,279 Cost: $500 |
$4,279 | 34,913 | - | - | - | - | - | - |
$4,279 34,913 kWh |
- - kW-months/year |
- - MMBtu |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $2,588 Cost: $1,342 |
$2,140 | 17,459 | $448 | 34 | - | - | - | - |
$2,140 17,459 kWh |
$448 34 kW-months/year |
- - MMBtu |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $112,736 Cost: $240,297 |
$25,414 | 207,327 | $13,162 | 987 | $40,335 | 4,582 | $33,825 | 3,000 | $25,414 207,327 kWh |
$13,162 987 kW-months/year |
$40,335 4,582 MMBtu |
$33,825 3,000 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: - Cost: - |
- | - | - | - | - | - | - | - | - - kWh |
- - kW-months/year |
- - MMBtu |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | MMBtu | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | LPG | Electricity Usage | Electricity Demand | Natural Gas | LPG |