IAC logo
IAC Assessment: CI0018
Sponsored by:
DOE MESC
IAC logo
IAC Assessment: CI0018
Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of California, Irvine
Assessment Year 2023
Principal Product Academic Service
NAICS 611110 - Elementary and Secondary Schools
SIC 8211 - Elementary And Secondary Schools
Sales <$500,000
# of Employees 122
Plant Area (Sq.Ft.) 216,563
Annual Production 1 Units
Production Hrs. Annual 1,500
Location (State) CA
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $254,721 1,585,714 kWh $0.16
Electricity Demand $111,413 6,474 kW-months/year $17.21
Electricity Fees $1,389 - $ -
Natural Gas $151,392 8,337 MMBtu $18.16
TOTAL ENERGY COSTS $518,915
RECOMMENDED SAVINGS* $349,734 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* -
#|Description Savings
Cost
Status Electricity Usage Electricity Demand One-time Revenue or Avoided Cost Electricity Usage Electricity Demand One-time Revenue or Avoided Cost
$ kWh $ kW-months/year $ $
01: 2.3141 USE BATTERY STORAGE FOR DEMAND CONTROL Savings:
$117,675
Cost:
$50,000
$49,905 309,586 $67,770 3,938 - - $49,905
309,586
kWh
$67,770
3,938
kW-months/year
-
-
$
02: 2.9114 USE SOLAR HEAT TO MAKE ELECTRICTY Savings:
$92,259
Cost:
$619,600
$77,803 482,650 $14,456 840 - - $77,803
482,650
kWh
$14,456
840
kW-months/year
-
-
$
03: 2.6231 UTILIZE CONTROLS TO OPERATE EQUIPMENT ONLY WHEN NEEDED Savings:
$15,348
Cost:
$2,000
$12,415 77,021 $2,933 170 - - $12,415
77,021
kWh
$2,933
170
kW-months/year
-
-
$
04: 2.1321 REPLACE FOSSIL FUEL EQUIPMENT WITH ELECTRICAL EQUIPMENT Savings:
$8,202
Cost:
$40,000
$8,202 50,877 - - - - $8,202
50,877
kWh
-
-
kW-months/year
-
-
$
05: 2.4322 USE OR REPLACE WITH ENERGY EFFICIENT SUBSTITUTES Savings:
$112,267
Cost:
$176,800
$6,187 52,134 - - $106,080 - $6,187
52,134
kWh
-
-
kW-months/year
$106,080
-
$
06: 2.4322 USE OR REPLACE WITH ENERGY EFFICIENT SUBSTITUTES Savings:
$3,377
Cost:
$45,000
$3,377 10,890 - - - - $3,377
10,890
kWh
-
-
kW-months/year
-
-
$
07: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$606
Cost:
$1,600
$193 1,200 $413 24 - - $193
1,200
kWh
$413
24
kW-months/year
-
-
$
TOTAL RECOMMENDED Savings:
$349,734
Cost:
$935,000
$158,082 984,358 $85,572 4,972 $106,080 - $158,082
984,358
kWh
$85,572
4,972
kW-months/year
$106,080
-
$
TOTAL IMPLEMENTED Savings:
-
Cost:
-
- - - - - - -
-
kWh
-
-
kW-months/year
-
-
$
Savings
Cost
$ kWh $ kW-months/year $ $
Electricity Usage Electricity Demand One-time Revenue or Avoided Cost Electricity Usage Electricity Demand One-time Revenue or Avoided Cost