Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Colorado State University |
---|---|
Assessment Year | 1999 |
Principal Product | air-cooled and water-cooled chillers |
NAICS | n/a |
SIC | 3585 - Refrigeration And Heating Equipment |
Sales | $100,000,000-$500,000,000 |
# of Employees | 900 |
Plant Area (Sq.Ft.) | 420,000 |
Annual Production | 7,500 Pieces |
Production Hrs. Annual | 5,434 |
Location (State) | CO |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $473,613 | 18,290,446 | kWh | $0.03 |
Electricity Demand | $323,063 | 40,557 | kW-months/year | $7.97 |
Electricity Fees | $3,192 | - | $ | - |
Natural Gas | $59,556 | 17,447 | MMBtu | $3.41 |
TOTAL ENERGY COSTS | $1,024,450 | |||
RECOMMENDED SAVINGS* | $94,890 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $66,690 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Other Liquid (non-haz) | Administrative Changes | Increase in Production | Electricity Usage | Electricity Demand | Natural Gas | Other Liquid (non-haz) | Administrative Changes | Increase in Production | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | gal | $ | $ | $ | % | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE |
Savings: $16,960 Cost: - |
$16,960 | 663,247 | - | - | - | - | - | - | - | - | - | - |
$16,960 663,247 kWh |
- - kW-months/year |
- - MMBtu |
- - gal |
- - $ |
- - % |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7314 REDUCE VENTILATION AIR |
Savings: $11,050 Cost: $12,600 |
- | - | - | - | $11,050 | 3,978 | - | - | - | - | - | - |
- - kWh |
- - kW-months/year |
$11,050 3,978 MMBtu |
- - gal |
- - $ |
- - % |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.8121 APPLY FOR TAX-FREE STATUS FOR ENERGY PURCHASES |
Savings: $7,900 Cost: $250 |
- | - | - | - | - | - | - | - | $7,900 | - | - | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
- - gal |
$7,900 - $ |
- - % |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.3191 USE DEMAND CONTROLLER OR LOAD SHEDDER |
Savings: $5,760 Cost: $2,000 |
- | - | $5,760 | 722 | - | - | - | - | - | - | - | - |
- - kWh |
$5,760 722 kW-months/year |
- - MMBtu |
- - gal |
- - $ |
- - % |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $2,660 Cost: $530 |
$1,450 | 54,807 | $1,210 | 50 | - | - | - | - | - | - | - | - |
$1,450 54,807 kWh |
$1,210 50 kW-months/year |
- - MMBtu |
- - gal |
- - $ |
- - % |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7442 KEEP DOORS AND WINDOWS SHUT WHEN NOT ON USE |
Savings: $2,210 Cost: $1,000 |
$900 | 34,291 | - | - | $1,310 | 470 | - | - | - | - | - | - |
$900 34,291 kWh |
- - kW-months/year |
$1,310 470 MMBtu |
- - gal |
- - $ |
- - % |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 3.6124 BURN WASTE OIL FOR HEAT |
Savings: $17,150 Cost: $10,500 |
$(-580) | (-22,567) | $(-310) | (-40) | $40 | 16 | $18,000 | 5,500 | - | - | - | - |
$(-580) (-22,567) kWh |
$(-310) (-40) kW-months/year |
$40 16 MMBtu |
$18,000 5,500 gal |
- - $ |
- - % |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 4.621 USE FIXTURES TO REDUCE MACHINE CHANGEOUT TIMES |
Savings: $31,200 Cost: $8,000 |
- | - | - | - | - | - | - | - | - | - | $31,200 | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
- - gal |
- - $ |
$31,200 - % |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $94,890 Cost: $34,880 |
$18,730 | 729,778 | $6,660 | 732 | $12,400 | 4,464 | $18,000 | 5,500 | $7,900 | - | $31,200 | - | $18,730 729,778 kWh |
$6,660 732 kW-months/year |
$12,400 4,464 MMBtu |
$18,000 5,500 gal |
$7,900 - $ |
$31,200 - % |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $66,690 Cost: $11,780 |
$19,310 | 752,345 | $6,970 | 772 | $1,310 | 470 | - | - | $7,900 | - | $31,200 | - | $19,310 752,345 kWh |
$6,970 772 kW-months/year |
$1,310 470 MMBtu |
- - gal |
$7,900 - $ |
$31,200 - % |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | gal | $ | $ | $ | % | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Other Liquid (non-haz) | Administrative Changes | Increase in Production | Electricity Usage | Electricity Demand | Natural Gas | Other Liquid (non-haz) | Administrative Changes | Increase in Production |