Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Colorado State University |
---|---|
Assessment Year | 2001 |
Principal Product | Napkins,bathroom tissue and paper bags |
NAICS | n/a |
SIC | 2674 - Bags: Uncoated Paper & Multiwall |
Sales | $50,000,000-$100,000,000 |
# of Employees | 150 |
Plant Area (Sq.Ft.) | 253,700 |
Annual Production | 24,000 Tons |
Production Hrs. Annual | 8,760 |
Location (State) | NM |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $233,639 | 5,372,000 | kWh | $0.04 |
Electricity Demand | $40,015 | 853 | kW-months/year | $46.91 |
Electricity Fees | $82,321 | - | $ | - |
Natural Gas | $29,828 | 3,785 | MMBtu | $7.88 |
TOTAL ENERGY COSTS | $385,803 | |||
RECOMMENDED SAVINGS* | $98,780 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $82,560 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | Ancillary Material Cost | Primary Product | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | Ancillary Material Cost | Primary Product | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | $ | $ | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7121 UTILIZE DAYLIGHT WHENEVER POSSIBLE IN LIEU OF ARTIFICIAL LIGHT |
Savings: $20,780 Cost: $61,010 |
$12,950 | 228,300 | $7,830 | 1,251 | - | - | - | - | - | - | - | - |
$12,950 228,300 kWh |
$7,830 1,251 kW-months/year |
- - MMBtu |
- - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT |
Savings: $10,820 Cost: $4,110 |
- | - | - | - | $10,820 | 1,389 | - | - | - | - | - | - |
- - kWh |
- - kW-months/year |
$10,820 1,389 MMBtu |
- - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $5,740 Cost: $570 |
$4,470 | 113,100 | $2,050 | 155 | - | - | $(-780) | - | - | - | - | - |
$4,470 113,100 kWh |
$2,050 155 kW-months/year |
- - MMBtu |
$(-780) - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4238 DO NOT USE COMPRESSED AIR FOR PERSONAL COOLING |
Savings: $3,630 Cost: $1,000 |
$2,050 | 51,900 | $1,580 | 120 | - | - | - | - | - | - | - | - |
$2,050 51,900 kWh |
$1,580 120 kW-months/year |
- - MMBtu |
- - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE |
Savings: $1,870 Cost: $1,300 |
$1,240 | 31,300 | $630 | 48 | - | - | - | - | - | - | - | - |
$1,240 31,300 kWh |
$630 48 kW-months/year |
- - MMBtu |
- - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $1,550 Cost: - |
$2,590 | 65,500 | $1,270 | 96 | - | - | $(-520) | - | $(-1,790) | - | - | - |
$2,590 65,500 kWh |
$1,270 96 kW-months/year |
- - MMBtu |
$(-520) - $ |
$(-1,790) - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $220 Cost: $210 |
$150 | 3,700 | $70 | 5 | - | - | - | - | - | - | - | - |
$150 3,700 kWh |
$70 5 kW-months/year |
- - MMBtu |
- - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 4.651 INSTALL BACK-UP EQUIPMENT |
Savings: $54,170 Cost: $84,380 |
- | - | - | - | - | - | - | - | - | - | $54,170 | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
- - $ |
$54,170 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $98,780 Cost: $152,580 |
$23,450 | 493,800 | $13,430 | 1,675 | $10,820 | 1,389 | $(-1,300) | - | $(-1,790) | - | $54,170 | - | $23,450 493,800 kWh |
$13,430 1,675 kW-months/year |
$10,820 1,389 MMBtu |
$(-1,300) - $ |
$(-1,790) - $ |
$54,170 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $82,560 Cost: $147,260 |
$18,660 | 372,700 | $10,510 | 1,454 | - | - | $(-780) | - | - | - | $54,170 | - | $18,660 372,700 kWh |
$10,510 1,454 kW-months/year |
- - MMBtu |
$(-780) - $ |
- - $ |
$54,170 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | $ | $ | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | Ancillary Material Cost | Primary Product | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | Ancillary Material Cost | Primary Product |