Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Colorado State University |
---|---|
Assessment Year | 2005 |
Principal Product | Can Press and Printing Machines |
NAICS | 333517 - Machine Tool Manufacturing |
SIC | 3542 - Machine Tools, Metal Forming Types |
Sales | $10,000,000-$50,000,000 |
# of Employees | 120 |
Plant Area (Sq.Ft.) | 93,360 |
Annual Production | 10 Pieces |
Production Hrs. Annual | 6,240 |
Location (State) | CO |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $53,007 | 1,762,400 | kWh | $0.03 |
Electricity Demand | $53,926 | 4,106 | kW-months/year | $13.13 |
Electricity Fees | $192 | - | $ | - |
Natural Gas | $30,216 | 3,830 | MMBtu | $7.89 |
TOTAL ENERGY COSTS | $137,341 | |||
RECOMMENDED SAVINGS* | $59,500 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $40,350 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | Ancillary Material Cost | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | Ancillary Material Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $1,670 Cost: $280 |
$1,060 | 30,100 | $610 | 46 | - | - | - | - | - | - |
$1,060 30,100 kWh |
$610 46 kW-months/year |
- - MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $35,290 Cost: $39,650 |
$9,000 | 255,500 | $6,480 | 491 | - | - | $5,840 | - | $13,970 | - |
$9,000 255,500 kWh |
$6,480 491 kW-months/year |
- - MMBtu |
$5,840 - $ |
$13,970 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.9111 USE SOLAR HEAT TO HEAT MAKE-UP AIR |
Savings: $11,250 Cost: $72,910 |
- | - | - | - | $11,250 | 1,557 | - | - | - | - |
- - kWh |
- - kW-months/year |
$11,250 1,557 MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7243 IMPROVE AIR CIRCULATION WITH DESTRATIFICATION FANS / OTHER METHODS |
Savings: $7,290 Cost: $25,470 |
$(-670) | (-19,000) | $(-340) | (-26) | $8,300 | 1,149 | - | - | - | - |
$(-670) (-19,000) kWh |
$(-340) (-26) kW-months/year |
$8,300 1,149 MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $2,090 Cost: $8,320 |
$750 | 21,200 | $1,140 | 86 | - | - | $70 | - | $130 | - |
$750 21,200 kWh |
$1,140 86 kW-months/year |
- - MMBtu |
$70 - $ |
$130 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $870 Cost: $3,510 |
$450 | 12,900 | $330 | 25 | - | - | $(-20) | - | $110 | - |
$450 12,900 kWh |
$330 25 kW-months/year |
- - MMBtu |
$(-20) - $ |
$110 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $610 Cost: $2,380 |
$530 | 14,900 | - | - | - | - | $50 | - | $30 | - |
$530 14,900 kWh |
- - kW-months/year |
- - MMBtu |
$50 - $ |
$30 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $430 Cost: $1,400 |
$40 | 1,000 | $10 | 1 | - | - | $120 | - | $260 | - |
$40 1,000 kWh |
$10 1 kW-months/year |
- - MMBtu |
$120 - $ |
$260 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $59,500 Cost: $153,920 |
$11,160 | 316,600 | $8,230 | 623 | $19,550 | 2,706 | $6,060 | - | $14,500 | - | $11,160 316,600 kWh |
$8,230 623 kW-months/year |
$19,550 2,706 MMBtu |
$6,060 - $ |
$14,500 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $40,350 Cost: $53,160 |
$11,300 | 320,700 | $8,570 | 649 | - | - | $6,010 | - | $14,470 | - | $11,300 320,700 kWh |
$8,570 649 kW-months/year |
- - MMBtu |
$6,010 - $ |
$14,470 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | Ancillary Material Cost | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | Ancillary Material Cost |