Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center Colorado State University
Assessment Year 2010
Principal Product Laser optics and assemblies
NAICS 333314 - Optical Instrument and Lens Manufacturing
SIC 3827 - Optical Instruments And Lenses
Sales $10,000,000-$50,000,000
# of Employees 180
Plant Area (Sq.Ft.) 65,000
Annual Production 780 Pieces
Production Hrs. Annual 4,680
Location (State) NM
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $121,057 2,687,904 kWh $0.05
Electricity Demand $92,046 6,286 kW-months/year $14.64
Natural Gas $4,786 589 MMBtu $8.13
TOTAL ENERGY COSTS $217,889
RECOMMENDED SAVINGS* $24,040 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* -
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Personnel Changes Administrative Changes Ancillary Material Cost Electricity Usage Electricity Demand Personnel Changes Administrative Changes Ancillary Material Cost
$ kWh $ kW-months/year $ $ $ $ $ $
01: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$3,720
Cost:
$410
$2,300 44,100 $1,420 104 - - - - - - $2,300
44,100
kWh
$1,420
104
kW-months/year
-
-
$
-
-
$
-
-
$
02: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS Savings:
$1,220
Cost:
$3,400
$880 18,900 $340 25 - - - - - - $880
18,900
kWh
$340
25
kW-months/year
-
-
$
-
-
$
-
-
$
03: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$5,910
Cost:
$5,160
$3,290 58,300 $2,690 197 $70 - - - $(-140) - $3,290
58,300
kWh
$2,690
197
kW-months/year
$70
-
$
-
-
$
$(-140)
-
$
04: 2.9114 USE SOLAR HEAT TO MAKE ELECTRICTY Savings:
$4,170
Cost:
$31,500
$1,020 16,800 $850 62 - - $2,300 - - - $1,020
16,800
kWh
$850
62
kW-months/year
-
-
$
$2,300
-
$
-
-
$
05: 2.6231 UTILIZE CONTROLS TO OPERATE EQUIPMENT ONLY WHEN NEEDED Savings:
$3,610
Cost:
$2,880
$3,610 78,300 - - - - - - - - $3,610
78,300
kWh
-
-
kW-months/year
-
-
$
-
-
$
-
-
$
06: 2.7232 REPLACE EXISTING HVAC UNIT WITH HIGH EFFICIENCY MODEL Savings:
$3,270
Cost:
$35,500
$2,650 53,300 $620 45 - - - - - - $2,650
53,300
kWh
$620
45
kW-months/year
-
-
$
-
-
$
-
-
$
07: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$1,300
Cost:
$5,160
$670 12,800 $410 30 $130 - - - $90 - $670
12,800
kWh
$410
30
kW-months/year
$130
-
$
-
-
$
$90
-
$
08: 2.7135 INSTALL OCCUPANCY SENSORS Savings:
$520
Cost:
$810
$280 4,800 $230 17 - - - - $10 - $280
4,800
kWh
$230
17
kW-months/year
-
-
$
-
-
$
$10
-
$
09: 2.6211 CONSERVE ENERGY BY EFFICIENT USE OF VENDING MACHINES Savings:
$320
Cost:
$650
$280 6,100 $40 3 - - - - - - $280
6,100
kWh
$40
3
kW-months/year
-
-
$
-
-
$
-
-
$
TOTAL RECOMMENDED Savings:
$24,040
Cost:
$85,470
$14,980 293,400 $6,600 483 $200 - $2,300 - $(-40) - $14,980
293,400
kWh
$6,600
483
kW-months/year
$200
-
$
$2,300
-
$
$(-40)
-
$
TOTAL IMPLEMENTED Savings:
-
Cost:
-
- - - - - - - - - - -
-
kWh
-
-
kW-months/year
-
-
$
-
-
$
-
-
$
Savings
Cost
$ kWh $ kW-months/year $ $ $ $ $ $
Electricity Usage Electricity Demand Personnel Changes Administrative Changes Ancillary Material Cost Electricity Usage Electricity Demand Personnel Changes Administrative Changes Ancillary Material Cost