Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center Colorado State University
Assessment Year 2016
Principal Product Family Entertainment Center
NAICS 713950 - Bowling Centers
SIC 7933 - Bowling Centers
Sales $1,000,000-$5,000,000
# of Employees 100
Plant Area (Sq.Ft.) 52,300
Annual Production 1,000 Units
Production Hrs. Annual 5,320
Location (State) CO
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $67,203 1,003,200 kWh $0.07
Electricity Demand $53,322 2,533 kW-months/year $21.05
Electricity Fees $876 - $ -
Natural Gas $22,060 4,042 MMBtu $5.46
TOTAL ENERGY COSTS $143,461
RECOMMENDED SAVINGS* $13,250 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* -
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Personnel Changes Ancillary Material Cost Electricity Usage Electricity Demand Personnel Changes Ancillary Material Cost
$ kWh $ kW-months/year $ $ $ $
01: 2.7252 UTILIZE AN EVAPORATIVE AIR PRE-COOLER OR OTHER HEAT EXCHANGER IN AC SYSTEM Savings:
$4,910
Cost:
$31,560
$1,290 19,200 $3,620 172 - - - - $1,290
19,200
kWh
$3,620
172
kW-months/year
-
-
$
-
-
$
02: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$4,020
Cost:
$13,690
$1,750 26,200 $1,340 64 $480 - $450 - $1,750
26,200
kWh
$1,340
64
kW-months/year
$480
-
$
$450
-
$
03: 2.9114 USE SOLAR HEAT TO MAKE ELECTRICTY Savings:
$2,820
Cost:
$14,180
$2,530 37,700 $290 14 - - - - $2,530
37,700
kWh
$290
14
kW-months/year
-
-
$
-
-
$
04: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS Savings:
$1,500
Cost:
$1,860
$1,050 15,600 $450 21 - - - - $1,050
15,600
kWh
$450
21
kW-months/year
-
-
$
-
-
$
TOTAL RECOMMENDED Savings:
$13,250
Cost:
$61,290
$6,620 98,700 $5,700 271 $480 - $450 - $6,620
98,700
kWh
$5,700
271
kW-months/year
$480
-
$
$450
-
$
TOTAL IMPLEMENTED Savings:
-
Cost:
-
- - - - - - - - -
-
kWh
-
-
kW-months/year
-
-
$
-
-
$
Savings
Cost
$ kWh $ kW-months/year $ $ $ $
Electricity Usage Electricity Demand Personnel Changes Ancillary Material Cost Electricity Usage Electricity Demand Personnel Changes Ancillary Material Cost