Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Delaware |
---|---|
Assessment Year | 2015 |
Principal Product | Plastics |
NAICS | 326121 - Unlaminated Plastics Profile Shape Manufacturing |
SIC | 3089 - Plastics Products, Nec |
Sales | $50,000,000-$100,000,000 |
# of Employees | 200 |
Plant Area (Sq.Ft.) | 134,500 |
Annual Production | 1,500,000,000 Pieces |
Production Hrs. Annual | 8,568 |
Location (State) | NJ |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $1,233,839 | 11,371,830 | kWh | $0.11 |
Electricity Demand | $159,563 | 21,134 | kW-months/year | $7.55 |
Electricity Fees | $29,949 | - | $ | - |
Natural Gas | $64,867 | 5,270 | MMBtu | $12.31 |
TOTAL ENERGY COSTS | $1,488,218 | |||
RECOMMENDED SAVINGS* | $116,607 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $17,831 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Electricity Usage | Electricity Demand | Natural Gas | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.4226 USE / PURCHASE OPTIMUM SIZED COMPRESSOR |
Savings: $48,766 Cost: $10,000 |
$44,416 | 411,260 | $4,350 | 576 | - | - |
$44,416 411,260 kWh |
$4,350 576 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE |
Savings: $10,440 Cost: - |
$9,564 | 88,560 | $876 | 116 | - | - |
$9,564 88,560 kWh |
$876 116 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.2623 MINIMIZE CONDENSER COOLING WATER TEMPERATURE |
Savings: $3,810 Cost: $700 |
$3,810 | 35,320 | - | - | - | - |
$3,810 35,320 kWh |
- - kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $14,618 Cost: $30,804 |
$13,318 | 123,320 | $1,300 | 172 | - | - |
$13,318 123,320 kWh |
$1,300 172 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $8,334 Cost: $9,600 |
$7,624 | 70,600 | $710 | 94 | - | - |
$7,624 70,600 kWh |
$710 94 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.6232 INSTALL SET-BACK TIMERS |
Savings: $6,174 Cost: $2,500 |
$5,629 | 52,125 | $545 | 72 | - | - |
$5,629 52,125 kWh |
$545 72 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7261 INSTALL TIMERS AND/OR THERMOSTATS |
Savings: $3,560 Cost: $300 |
$1,580 | 14,700 | - | - | $1,980 | 161 |
$1,580 14,700 kWh |
- - kW-months/year |
$1,980 161 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $3,831 Cost: $40,000 |
$3,216 | 29,780 | $615 | 82 | - | - |
$3,216 29,780 kWh |
$615 82 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT |
Savings: $17,074 Cost: $64,980 |
- | - | - | - | $17,074 | 1,387 |
- - kWh |
- - kW-months/year |
$17,074 1,387 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $116,607 Cost: $158,884 |
$89,157 | 825,665 | $8,396 | 1,112 | $19,054 | 1,548 | $89,157 825,665 kWh |
$8,396 1,112 kW-months/year |
$19,054 1,548 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $17,831 Cost: $40,300 |
$14,360 | 133,040 | $1,491 | 198 | $1,980 | 161 | $14,360 133,040 kWh |
$1,491 198 kW-months/year |
$1,980 161 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Electricity Usage | Electricity Demand | Natural Gas |