IAC logo
IAC Assessment: DL0162
Sponsored by:
DOE MESC
IAC logo
IAC Assessment: DL0162
Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of Delaware
Assessment Year 2016
Principal Product Analytical Equipment
NAICS 334516 - Analytical Laboratory Instrument Manufacturing
SIC 3826 - Analytical Instruments
Sales $50,000,000-$100,000,000
# of Employees 85
Plant Area (Sq.Ft.) 37,500
Annual Production 30,000 Pieces
Production Hrs. Annual 7,114
Location (State) DE
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $363,335 4,003,929 kWh $0.09
Natural Gas $80,146 8,809 MMBtu $9.10
TOTAL ENERGY COSTS $477,800
RECOMMENDED SAVINGS* $65,640 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $61,270
#|Description Savings
Cost
Status Electricity Usage Natural Gas Other Liquid (non-haz) Electricity Usage Natural Gas Other Liquid (non-haz)
$ kWh $ MMBtu $ gal
01: 2.7224 REDUCE SPACE CONDITIONING DURING NON-WORKING HOURS Savings:
$22,170
Cost:
-
$5,700 62,605 $16,470 1,810 - - $5,700
62,605
kWh
$16,470
1,810
MMBtu
-
-
gal
02: 2.6212 TURN OFF EQUIPMENT DURING BREAKS, REDUCE OPERATING TIME Savings:
$7,660
Cost:
-
$880 9,680 $6,780 745 - - $880
9,680
kWh
$6,780
745
MMBtu
-
-
gal
03: 2.7314 REDUCE VENTILATION AIR Savings:
$2,430
Cost:
$340
$1,390 15,280 $1,040 114 - - $1,390
15,280
kWh
$1,040
114
MMBtu
-
-
gal
04: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE Savings:
$3,605
Cost:
$800
$2,640 29,040 - - $965 260,000 $2,640
29,040
kWh
-
-
MMBtu
$965
260,000
gal
05: 2.6212 TURN OFF EQUIPMENT DURING BREAKS, REDUCE OPERATING TIME Savings:
$1,940
Cost:
$510
$1,940 21,330 - - - - $1,940
21,330
kWh
-
-
MMBtu
-
-
gal
06: 3.4114 REPLACE CITY WATER WITH RECYCLED WATER VIA COOLING TOWER Savings:
$18,175
Cost:
$10,500
$(-560) (-6,170) - - $18,735 5,050,000 $(-560)
(-6,170)
kWh
-
-
MMBtu
$18,735
5,050,000
gal
07: 2.6231 UTILIZE CONTROLS TO OPERATE EQUIPMENT ONLY WHEN NEEDED Savings:
$1,730
Cost:
$1,820
- - $1,730 190 - - -
-
kWh
$1,730
190
MMBtu
-
-
gal
08: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$7,930
Cost:
$29,230
$7,930 87,130 - - - - $7,930
87,130
kWh
-
-
MMBtu
-
-
gal
TOTAL RECOMMENDED Savings:
$65,640
Cost:
$43,200
$19,920 218,895 $26,020 2,859 $19,700 5,310,000 $19,920
218,895
kWh
$26,020
2,859
MMBtu
$19,700
5,310,000
gal
TOTAL IMPLEMENTED Savings:
$61,270
Cost:
$42,350
$16,590 182,285 $24,980 2,745 $19,700 5,310,000 $16,590
182,285
kWh
$24,980
2,745
MMBtu
$19,700
5,310,000
gal
Savings
Cost
$ kWh $ MMBtu $ gal
Electricity Usage Natural Gas Other Liquid (non-haz) Electricity Usage Natural Gas Other Liquid (non-haz)