Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of Delaware
Assessment Year 2021
Principal Product Plastic Tubes
NAICS 326121 - Unlaminated Plastics Profile Shape Manufacturing
SIC 3082 - Unsupported Plastics Profile Shapes
Sales $10,000,000-$50,000,000
# of Employees 41
Plant Area (Sq.Ft.) 75,000
Annual Production 400,000 Thousand Feet
Production Hrs. Annual 5,616
Location (State) DE
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $172,240 2,060,902 kWh $0.08
Electricity Demand $34,325 5,452 kW-months/year $6.30
LPG $6,838 440 MMBtu $15.54
TOTAL ENERGY COSTS $213,403
RECOMMENDED SAVINGS* $30,114 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $16,160
#|Description Savings
Cost
Status Electricity Usage Electricity Usage
$ kWh
01: 2.4222 INSTALL ADEQUATE DRYERS ON AIR LINES TO ELIMINATE BLOWDOWN Savings:
$5,944
Cost:
$6,452
$5,944 72,491 $5,944
72,491
kWh
02: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE Savings:
$849
Cost:
-
$849 10,358 $849
10,358
kWh
03: 2.7261 INSTALL TIMERS AND/OR THERMOSTATS Savings:
$509
Cost:
$165
$509 6,211 $509
6,211
kWh
04: 2.6211 CONSERVE ENERGY BY EFFICIENT USE OF VENDING MACHINES Savings:
$110
Cost:
$20
$110 1,340 $110
1,340
kWh
05: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM Savings:
$1,762
Cost:
$1,037
$1,762 21,485 $1,762
21,485
kWh
06: 2.2511 INSULATE BARE EQUIPMENT Savings:
$1,842
Cost:
$2,864
$1,842 22,464 $1,842
22,464
kWh
07: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$13,469
Cost:
$18,418
$13,469 164,255 $13,469
164,255
kWh
08: 2.2614 USE COOLING TOWER OR ECONOMIZER TO REPLACE CHILLER COOLING Savings:
$5,629
Cost:
$13,777
$5,629 68,646 $5,629
68,646
kWh
TOTAL RECOMMENDED Savings:
$30,114
Cost:
$42,733
$30,114 367,250 $30,114
367,250
kWh
TOTAL IMPLEMENTED Savings:
$16,160
Cost:
$21,282
$16,160 197,077 $16,160
197,077
kWh
Savings
Cost
$ kWh
Electricity Usage Electricity Usage