IAC logo
IAC Assessment: GT0838
Sponsored by:
DOE MESC
IAC logo
IAC Assessment: GT0838
Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center Georgia Institute of Technology
Assessment Year 2007
Principal Product Rubber Backed Floor Mats
NAICS 314110 - Carpet and Rug Mills
SIC 2273 - Carpets And Rugs
Sales $50,000,000-$100,000,000
# of Employees 240
Plant Area (Sq.Ft.) 190,000
Annual Production 41,400 Thousand Feet
Production Hrs. Annual 6,864
Location (State) GA
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $100,306 2,865,872 kWh $0.04
Electricity Demand $109,609 6,172 kW-months/year $17.76
Natural Gas $473,220 53,676 MMBtu $8.82
TOTAL ENERGY COSTS $683,135
RECOMMENDED SAVINGS* $114,705 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* -
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Natural Gas Water Disposal Administrative Changes Electricity Usage Electricity Demand Natural Gas Water Disposal Administrative Changes
$ kWh $ kW-months/year $ MMBtu $ Tgal $ $
01: 2.4322 USE OR REPLACE WITH ENERGY EFFICIENT SUBSTITUTES Savings:
$25,825
Cost:
$10,000
$13,685 391,008 $12,140 684 - - - - - - $13,685
391,008
kWh
$12,140
684
kW-months/year
-
-
MMBtu
-
-
Tgal
-
-
$
02: 2.2212 USE MINIMUM SAFE OVEN VENTILATION Savings:
$5,955
Cost:
$6,000
$178 5,088 $141 8 $5,636 612 - - - - $178
5,088
kWh
$141
8
kW-months/year
$5,636
612
MMBtu
-
-
Tgal
-
-
$
03: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE Savings:
$7,976
Cost:
-
- - - - $7,976 766 - - - - -
-
kWh
-
-
kW-months/year
$7,976
766
MMBtu
-
-
Tgal
-
-
$
04: 2.1233 ANALYZE FLUE GAS FOR PROPER AIR/FUEL RATIO Savings:
$3,908
Cost:
-
- - - - $4,808 522 - - $(-900) - -
-
kWh
-
-
kW-months/year
$4,808
522
MMBtu
-
-
Tgal
$(-900)
-
$
05: 2.2163 USE MINIMUM STEAM OPERATING PRESSURE Savings:
$17,020
Cost:
-
- - - - $17,020 1,848 - - - - -
-
kWh
-
-
kW-months/year
$17,020
1,848
MMBtu
-
-
Tgal
-
-
$
06: 2.1241 REDUCE EXCESSIVE BOILER BLOWDOWN Savings:
$1,288
Cost:
$3,975
- - - - $1,050 114 $238 39,000 - - -
-
kWh
-
-
kW-months/year
$1,050
114
MMBtu
$238
39,000
Tgal
-
-
$
07: 2.7224 REDUCE SPACE CONDITIONING DURING NON-WORKING HOURS Savings:
$2,338
Cost:
$2,250
$2,338 66,792 - - - - - - - - $2,338
66,792
kWh
-
-
kW-months/year
-
-
MMBtu
-
-
Tgal
-
-
$
08: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$39,896
Cost:
$127,725
$21,141 604,032 $18,755 1,056 - - - - - - $21,141
604,032
kWh
$18,755
1,056
kW-months/year
-
-
MMBtu
-
-
Tgal
-
-
$
09: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$8,159
Cost:
$17,436
$4,323 123,552 $3,836 216 - - - - - - $4,323
123,552
kWh
$3,836
216
kW-months/year
-
-
MMBtu
-
-
Tgal
-
-
$
10: 2.2511 INSULATE BARE EQUIPMENT Savings:
$2,340
Cost:
$2,004
- - - - $2,340 254 - - - - -
-
kWh
-
-
kW-months/year
$2,340
254
MMBtu
-
-
Tgal
-
-
$
TOTAL RECOMMENDED Savings:
$114,705
Cost:
$169,390
$41,665 1,190,472 $34,872 1,964 $38,830 4,116 $238 39,000 $(-900) - $41,665
1,190,472
kWh
$34,872
1,964
kW-months/year
$38,830
4,116
MMBtu
$238
39,000
Tgal
$(-900)
-
$
TOTAL IMPLEMENTED Savings:
-
Cost:
-
- - - - - - - - - - -
-
kWh
-
-
kW-months/year
-
-
MMBtu
-
-
Tgal
-
-
$
Savings
Cost
$ kWh $ kW-months/year $ MMBtu $ Tgal $ $
Electricity Usage Electricity Demand Natural Gas Water Disposal Administrative Changes Electricity Usage Electricity Demand Natural Gas Water Disposal Administrative Changes