IAC Center Georgia Institute of Technology
Assessment Year 2017
Principal Product Light Fixtures
NAICS 335122 - Commercial, Industrial, and Institutional Electric Lighting Fixture Manufacturing
SIC 3646 - Commercial Lighting Fixtures
Sales $67,000,000
# of Employees 219
Plant Area (Sq.Ft.) 523,000
Annual Production 1,420,000 not found
Production Hrs. Annual 4,800
Location (State) GA
Source Yearly Cost Usage
Electricity Usage $599,743 5,804,609
Natural Gas $70,883 15,887
TOTAL ENERGY COSTS $670,626
RECOMMENDED SAVINGS* $229,262 *Non-energy impacts
included in savings.
IMPLEMENTED SAVINGS* $72,949
#|Description Status Electricity Usage Electricity Usage
$ kWh
01: 2.4235 REMOVE OR CLOSE OFF UNNEEDED COMPRESSED AIR LINES Savings:
$35,273
Cost:
$4,360
$35,273 458,100 $35,273
458,100
kWh
02: 2.4232 ELIMINATE OR REDUCE COMPRESSED AIR USED FOR COOLING, AGITATING LIQUIDS, MOVING PRODUCT, OR DRYING Savings:
$1,819
Cost:
$4,560
$1,819 23,619 $1,819
23,619
kWh
03: 2.7261 INSTALL TIMERS AND/OR THERMOSTATS Savings:
$4,720
Cost:
$11,140
$4,720 61,295 $4,720
61,295
kWh
04: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$68,229
Cost:
$85,688
$68,229 886,096 $68,229
886,096
kWh
05: 2.9114 USE SOLAR HEAT TO MAKE ELECTRICTY Savings:
$110,000
Cost:
$429,000
$110,000 1,430,520 $110,000
1,430,520
kWh
06: 2.7261 INSTALL TIMERS AND/OR THERMOSTATS Savings:
$5,005
Cost:
$5,200
$5,005 65,000 $5,005
65,000
kWh
07: 2.4143 USE ADJUSTABLE FREQUENCY DRIVE TO REPLACE THROTTLING SYSTEM Savings:
$4,216
Cost:
$6,000
$4,216 54,762 $4,216
54,762
kWh
TOTAL RECOMMENDED Savings:
$229,262
Cost:
$545,948
$229,262 2,979,392 -
-
kWh
TOTAL IMPLEMENTED Savings:
$72,949
Cost:
$96,828
$72,949 947,391 -
-
kWh
$ kWh