Select a Center

Arizona State University
Boise State University
Case Western Reserve University
Clemson University
Colorado State University
Georgia Institute of Technology
Indiana University-Purdue University
Lehigh University
Louisiana State University
North Carolina State
Oklahoma State University
Oregon State University
San Diego State University
San Francisco State University
Syracuse University
Tennessee Technological University
Texas A&M, College Station
University of Alabama
University of Dayton
University of Delaware
University of Florida
University of Illinois, Chicago
University of Kentucky
University of Massachusetts
University of Miami
University of Missouri-Columbia
University of Nebraska–Lincoln
University of Texas Rio Grande Valley
University of Utah
University of Wisconsin, Milwaukee
West Virginia University
IAC logo
IAC Assessment: GT0931
Sponsored by:
EERE AMO
IAC logo
IAC Assessment: GT0931
IAC Center Georgia Institute of Technology
Assessment Year 2019
Principal Product Carpet and Vinyl Flooring
NAICS 314110 - Carpet and Rug Mills
SIC 2273 - Carpets And Rugs
Sales $56,300,000
# of Employees 264
Plant Area (Sq.Ft.) 154,900
Annual Production 17,918,625 Pieces
Production Hrs. Annual 6,240
Location (State) GA
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $169,907 3,264,000 kWh $0.05
Natural Gas $37,518 5,274 MMBtu $7.11
TOTAL ENERGY COSTS $207,425
RECOMMENDED SAVINGS* $110,485 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $35,746
#|Description Savings
Cost
Status Electricity Usage Personnel Changes Electricity Usage Personnel Changes
$ kWh $ $
01: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$12,292
Cost:
$3,500
$12,292 236,378 - - $12,292
236,378
kWh
-
-
$
02: 2.7135 INSTALL OCCUPANCY SENSORS Savings:
$2,451
Cost:
$1,382
$2,451 47,126 - - $2,451
47,126
kWh
-
-
$
03: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$19,194
Cost:
$25,005
$19,194 369,115 - - $19,194
369,115
kWh
-
-
$
04: 2.7243 IMPROVE AIR CIRCULATION WITH DESTRATIFICATION FANS / OTHER METHODS Savings:
$7,893
Cost:
$19,194
$7,893 151,781 - - $7,893
151,781
kWh
-
-
$
05: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE Savings:
$1,664
Cost:
$4,500
$1,664 32,009 - - $1,664
32,009
kWh
-
-
$
06: 2.7232 REPLACE EXISTING HVAC UNIT WITH HIGH EFFICIENCY MODEL Savings:
$14,047
Cost:
$39,068
$1,547 29,746 $12,500 - $1,547
29,746
kWh
$12,500
-
$
07: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS Savings:
$111
Cost:
$322
$111 2,131 - - $111
2,131
kWh
-
-
$
08: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE Savings:
$34
Cost:
$131
$34 660 - - $34
660
kWh
-
-
$
09: 2.9114 USE SOLAR HEAT TO MAKE ELECTRICTY Savings:
$52,800
Cost:
$554,400
$52,800 1,015,399 - - $52,800
1,015,399
kWh
-
-
$
TOTAL RECOMMENDED Savings:
$110,485
Cost:
$647,502
$97,985 1,884,345 $12,500 - $97,985
1,884,345
kWh
$12,500
-
$
TOTAL IMPLEMENTED Savings:
$35,746
Cost:
$34,840
$35,746 687,419 - - $35,746
687,419
kWh
-
-
$
Savings
Cost
$ kWh $ $
Electricity Usage Personnel Changes Electricity Usage Personnel Changes