Select a Center

Arizona State University
Case Western Reserve University
Colorado School of Mines
Colorado State University
Indiana University-Purdue University
Kennesaw State
Lehigh University
Louisiana State University
Louisiana Tech
Michigan State University
Mississippi State
Oklahoma State University
Oregon State University
San Francisco State University
Syracuse University
Tennessee Technological University
Texas A&M, College Station
University of Alabama
University of California, Irvine
University of Connecticut
University of Dayton
University of Delaware
University of Florida
University of Illinois, Chicago
University of Louisville
University of Massachusetts
University of Miami
University of Missouri-Columbia
University of Nebraska–Lincoln
University of North Carolina, Charlotte
University of Texas Rio Grande Valley
University of Utah
University of Washington
University of Wisconsin, Milwaukee
West Virginia University
IAC logo
IAC Assessment: GT0931
Sponsored by:
EERE AMO
IAC logo
IAC Assessment: GT0931
IAC Center Georgia Institute of Technology
Assessment Year 2019
Principal Product Carpet and Vinyl Flooring
NAICS 314110 - Carpet and Rug Mills
SIC 2273 - Carpets And Rugs
Sales $50,000,000-$100,000,000
# of Employees 264
Plant Area (Sq.Ft.) 154,900
Annual Production 17,918,625 Pieces
Production Hrs. Annual 6,240
Location (State) GA
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $169,907 3,264,000 kWh $0.05
Natural Gas $37,518 5,274 MMBtu $7.11
TOTAL ENERGY COSTS $207,425
RECOMMENDED SAVINGS* $110,485 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $35,746
#|Description Savings
Cost
Status Electricity Usage Personnel Changes Electricity Usage Personnel Changes
$ kWh $ $
01: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$12,292
Cost:
$3,500
$12,292 236,378 - - $12,292
236,378
kWh
-
-
$
02: 2.7135 INSTALL OCCUPANCY SENSORS Savings:
$2,451
Cost:
$1,382
$2,451 47,126 - - $2,451
47,126
kWh
-
-
$
03: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$19,194
Cost:
$25,005
$19,194 369,115 - - $19,194
369,115
kWh
-
-
$
04: 2.7243 IMPROVE AIR CIRCULATION WITH DESTRATIFICATION FANS / OTHER METHODS Savings:
$7,893
Cost:
$19,194
$7,893 151,781 - - $7,893
151,781
kWh
-
-
$
05: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE Savings:
$1,664
Cost:
$4,500
$1,664 32,009 - - $1,664
32,009
kWh
-
-
$
06: 2.7232 REPLACE EXISTING HVAC UNIT WITH HIGH EFFICIENCY MODEL Savings:
$14,047
Cost:
$39,068
$1,547 29,746 $12,500 - $1,547
29,746
kWh
$12,500
-
$
07: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS Savings:
$111
Cost:
$322
$111 2,131 - - $111
2,131
kWh
-
-
$
08: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE Savings:
$34
Cost:
$131
$34 660 - - $34
660
kWh
-
-
$
09: 2.9114 USE SOLAR HEAT TO MAKE ELECTRICTY Savings:
$52,800
Cost:
$554,400
$52,800 1,015,399 - - $52,800
1,015,399
kWh
-
-
$
TOTAL RECOMMENDED Savings:
$110,485
Cost:
$647,502
$97,985 1,884,345 $12,500 - $97,985
1,884,345
kWh
$12,500
-
$
TOTAL IMPLEMENTED Savings:
$35,746
Cost:
$34,840
$35,746 687,419 - - $35,746
687,419
kWh
-
-
$
Savings
Cost
$ kWh $ $
Electricity Usage Personnel Changes Electricity Usage Personnel Changes