Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center Iowa State University
Assessment Year 2004
Principal Product processed beef
NAICS 311611 - Animal (except Poultry) Slaughtering
SIC 2011 - Meat Packing Plants
Sales $50,000,000-$100,000,000
# of Employees 125
Plant Area (Sq.Ft.) 43,000
Annual Production 83,200 Pieces
Production Hrs. Annual 6,240
Location (State) MN
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $131,004 3,858,000 kWh $0.03
Electricity Demand $67,299 8,880 kW-months/year $7.58
Natural Gas $204,854 29,400 MMBtu $6.97
TOTAL ENERGY COSTS $403,157
RECOMMENDED SAVINGS* $17,580 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* -
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Natural Gas Electricity Usage Electricity Demand Natural Gas
$ kWh $ kW-months/year $ MMBtu
01: 2.2427 USE WASTE HEAT FROM HOT FLUE GASES TO PREHEAT INCOMING FLUIDS Savings:
$6,831
Cost:
$13,500
- - - - $6,831 980 -
-
kWh
-
-
kW-months/year
$6,831
980
MMBtu
02: 2.2449 RECOVER HEAT FROM EXHAUSTED STEAM, HOT AIR OR HOT WATER Savings:
$1,161
Cost:
$2,300
- - - - $1,161 151 -
-
kWh
-
-
kW-months/year
$1,161
151
MMBtu
03: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$1,472
Cost:
$254
$848 25,082 $624 65 - - $848
25,082
kWh
$624
65
kW-months/year
-
-
MMBtu
04: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS Savings:
$997
Cost:
$166
$582 17,113 $415 46 - - $582
17,113
kWh
$415
46
kW-months/year
-
-
MMBtu
05: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED Savings:
$413
Cost:
$25
$238 7,020 $175 18 - - $238
7,020
kWh
$175
18
kW-months/year
-
-
MMBtu
06: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT Savings:
$913
Cost:
$857
- - - - $913 131 -
-
kWh
-
-
kW-months/year
$913
131
MMBtu
07: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM Savings:
$2,449
Cost:
$7,025
$1,412 41,652 $1,037 107 - - $1,412
41,652
kWh
$1,037
107
kW-months/year
-
-
MMBtu
08: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$1,027
Cost:
$198
$696 20,545 $331 3 - - $696
20,545
kWh
$331
3
kW-months/year
-
-
MMBtu
09: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$2,065
Cost:
$4,616
$1,228 36,300 $837 86 - - $1,228
36,300
kWh
$837
86
kW-months/year
-
-
MMBtu
10: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS Savings:
$252
Cost:
$630
$181 7,972 $71 11 - - $181
7,972
kWh
$71
11
kW-months/year
-
-
MMBtu
TOTAL RECOMMENDED Savings:
$17,580
Cost:
$29,571
$5,185 155,684 $3,490 336 $8,905 1,262 $5,185
155,684
kWh
$3,490
336
kW-months/year
$8,905
1,262
MMBtu
TOTAL IMPLEMENTED Savings:
-
Cost:
-
- - - - - - -
-
kWh
-
-
kW-months/year
-
-
MMBtu
Savings
Cost
$ kWh $ kW-months/year $ MMBtu
Electricity Usage Electricity Demand Natural Gas Electricity Usage Electricity Demand Natural Gas