Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Illinois, Chicago |
---|---|
Assessment Year | 2001 |
Principal Product | Screen Printed Banners & POP Displays |
NAICS | n/a |
SIC | 2399 - Fabricated Textile Products, Nec |
Sales | $5,000,000-$10,000,000 |
# of Employees | 65 |
Plant Area (Sq.Ft.) | 60,000 |
Annual Production | 2,500,000 Pieces |
Production Hrs. Annual | 2,496 |
Location (State) | IL |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $38,012 | 1,087,724 | kWh | $0.03 |
Electricity Demand | $104,794 | 8,264 | kW-months/year | $12.68 |
Electricity Fees | $10,775 | - | $ | - |
Natural Gas | $69,941 | 8,570 | MMBtu | $8.16 |
TOTAL ENERGY COSTS | $235,010 | |||
RECOMMENDED SAVINGS* | $88,599 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | - |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | Administrative Changes | Ancillary Material Cost | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | Administrative Changes | Ancillary Material Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | $ | $ | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS |
Savings: $159 Cost: $245 |
$60 | 1,700 | $99 | 8 | - | - | - | - | - | - | - | - |
$60 1,700 kWh |
$99 8 kW-months/year |
- - MMBtu |
- - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $996 Cost: $2,273 |
$235 | 6,728 | $112 | 9 | - | - | $470 | - | - | - | $179 | - |
$235 6,728 kWh |
$112 9 kW-months/year |
- - MMBtu |
$470 - $ |
- - $ |
$179 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $4,581 Cost: $24,034 |
$1,668 | 47,647 | $2,913 | 239 | - | - | - | - | - | - | - | - |
$1,668 47,647 kWh |
$2,913 239 kW-months/year |
- - MMBtu |
- - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.2511 INSULATE BARE EQUIPMENT |
Savings: $1,227 Cost: $2,450 |
- | - | - | - | $1,227 | 150 | - | - | - | - | - | - |
- - kWh |
- - kW-months/year |
$1,227 150 MMBtu |
- - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT |
Savings: $1,736 Cost: $2,070 |
- | - | - | - | $1,736 | 231 | - | - | - | - | - | - |
- - kWh |
- - kW-months/year |
$1,736 231 MMBtu |
- - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 4.322 ELIMINATE OLD STOCK AND MODIFY INVENTORY CONTROL |
Savings: $22,400 Cost: $6,000 |
- | - | - | - | - | - | - | - | $22,400 | - | - | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
$22,400 - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 4.447 AUTOMATE PAYROLL SYSTEM |
Savings: $57,500 Cost: $8,600 |
- | - | - | - | - | - | $55,500 | - | $2,000 | - | - | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
$55,500 - $ |
$2,000 - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $88,599 Cost: $45,672 |
$1,963 | 56,075 | $3,124 | 256 | $2,963 | 381 | $55,970 | - | $24,400 | - | $179 | - | $1,963 56,075 kWh |
$3,124 256 kW-months/year |
$2,963 381 MMBtu |
$55,970 - $ |
$24,400 - $ |
$179 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: - Cost: - |
- | - | - | - | - | - | - | - | - | - | - | - | - - kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | $ | $ | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | Administrative Changes | Ancillary Material Cost | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | Administrative Changes | Ancillary Material Cost |