Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Illinois, Chicago |
---|---|
Assessment Year | 2009 |
Principal Product | Toaster Pastries and Baked Goods |
NAICS | 311821 - Cookie and Cracker Manufacturing |
SIC | 2052 - Cookies And Crackers |
Sales | $5,000,000-$10,000,000 |
# of Employees | 300 |
Plant Area (Sq.Ft.) | 311,300 |
Annual Production | 86,950,000 Pounds |
Production Hrs. Annual | 6,808 |
Location (State) | IL |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $829,890 | 10,920,301 | kWh | $0.08 |
Electricity Demand | $118,152 | 21,993 | kW-months/year | $5.37 |
Natural Gas | $912,152 | 193,754 | MMBtu | $4.71 |
TOTAL ENERGY COSTS | $1,896,217 | |||
RECOMMENDED SAVINGS* | $54,484 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $42,693 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Electricity Usage | Electricity Demand | Natural Gas | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7131 ADD AREA LIGHTING SWITCHES |
Savings: $10,860 Cost: $8,096 |
$9,898 | 130,237 | $962 | 178 | - | - |
$9,898 130,237 kWh |
$962 178 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $4,252 Cost: $4,247 |
$3,786 | 49,820 | $466 | 87 | - | - |
$3,786 49,820 kWh |
$466 87 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $1,116 Cost: $1,649 |
$906 | 11,908 | $210 | 39 | - | - |
$906 11,908 kWh |
$210 39 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7122 DISCONNECT BALLASTS |
Savings: $2,089 Cost: $2,200 |
$1,858 | 24,444 | $231 | 43 | - | - |
$1,858 24,444 kWh |
$231 43 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $14,483 Cost: $29,250 |
$12,808 | 168,519 | $1,675 | 312 | - | - |
$12,808 168,519 kWh |
$1,675 312 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $1,309 Cost: $5,917 |
$1,191 | 16,320 | $118 | 22 | - | - |
$1,191 16,320 kWh |
$118 22 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.4151 DEVELOP A REPAIR/REPLACE POLICY |
Savings: $4,792 Cost: $15,044 |
$4,261 | 56,054 | $531 | 99 | - | - |
$4,261 56,054 kWh |
$531 99 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $3,513 Cost: $1,610 |
$3,513 | 44,694 | - | - | - | - |
$3,513 44,694 kWh |
- - kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.4226 USE / PURCHASE OPTIMUM SIZED COMPRESSOR |
Savings: $8,278 Cost: $7,995 |
$8,278 | 108,928 | - | - | - | - |
$8,278 108,928 kWh |
- - kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.6211 CONSERVE ENERGY BY EFFICIENT USE OF VENDING MACHINES |
Savings: $934 Cost: - |
$547 | 7,200 | $387 | 72 | - | - |
$547 7,200 kWh |
$387 72 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
11: 2.2136 INSTALL / REPAIR INSULATION ON STEAM LINES |
Savings: $1,559 Cost: $2,887 |
- | - | - | - | $1,559 | 359 |
- - kWh |
- - kW-months/year |
$1,559 359 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
12: 2.7261 INSTALL TIMERS AND/OR THERMOSTATS |
Savings: $1,299 Cost: - |
- | - | - | - | $1,299 | 155 |
- - kWh |
- - kW-months/year |
$1,299 155 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $54,484 Cost: $78,895 |
$47,046 | 618,124 | $4,580 | 852 | $2,858 | 514 | $47,046 618,124 kWh |
$4,580 852 kW-months/year |
$2,858 514 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $42,693 Cost: $69,290 |
$35,255 | 464,502 | $4,580 | 852 | $2,858 | 514 | $35,255 464,502 kWh |
$4,580 852 kW-months/year |
$2,858 514 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Electricity Usage | Electricity Demand | Natural Gas |