Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Illinois, Chicago |
---|---|
Assessment Year | 2011 |
Principal Product | Food |
NAICS | 311211 - Flour Milling |
SIC | 2041 - Flour And Other Grain Mill Products |
Sales | $50,000,000-$100,000,000 |
# of Employees | 85 |
Plant Area (Sq.Ft.) | 126,800 |
Annual Production | 30,608,773 Pounds |
Production Hrs. Annual | 4,488 |
Location (State) | IL |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $171,763 | 1,998,200 | kWh | $0.09 |
Electricity Demand | $31,010 | 6,720 | kW-months/year | $4.61 |
Electricity Fees | $2,700 | - | $ | - |
Natural Gas | $1,504 | 181 | MMBtu | $8.31 |
TOTAL ENERGY COSTS | $208,740 | |||
RECOMMENDED SAVINGS* | $30,960 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | - |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | Administrative Changes | Ancillary Material Cost | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | Administrative Changes | Ancillary Material Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | $ | $ | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $3,319 Cost: - |
$3,042 | 35,366 | $404 | 88 | - | - | - | - | $171 | - | $(-298) | - |
$3,042 35,366 kWh |
$404 88 kW-months/year |
- - MMBtu |
- - $ |
$171 - $ |
$(-298) - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $160 Cost: $503 |
$144 | 1,680 | $18 | 4 | - | - | $2 | - | - | - | $(-4) | - |
$144 1,680 kWh |
$18 4 kW-months/year |
- - MMBtu |
$2 - $ |
- - $ |
$(-4) - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $328 Cost: $2,003 |
$271 | 3,152 | $57 | 12 | - | - | - | - | - | - | - | - |
$271 3,152 kWh |
$57 12 kW-months/year |
- - MMBtu |
- - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $14,540 Cost: $81,305 |
$12,793 | 148,760 | $1,578 | 342 | - | - | $246 | - | - | - | $(-77) | - |
$12,793 148,760 kWh |
$1,578 342 kW-months/year |
- - MMBtu |
$246 - $ |
- - $ |
$(-77) - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $11,481 Cost: $43,841 |
$9,416 | 109,484 | $1,161 | 252 | - | - | $42 | - | - | - | $862 | - |
$9,416 109,484 kWh |
$1,161 252 kW-months/year |
- - MMBtu |
$42 - $ |
- - $ |
$862 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $182 Cost: $426 |
$145 | 1,682 | $11 | 2 | - | - | - | - | - | - | $26 | - |
$145 1,682 kWh |
$11 2 kW-months/year |
- - MMBtu |
- - $ |
- - $ |
$26 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $363 Cost: - |
$363 | 4,225 | - | - | - | - | - | - | - | - | - | - |
$363 4,225 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $570 Cost: $1,035 |
$570 | 6,629 | - | - | - | - | - | - | - | - | - | - |
$570 6,629 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.7224 REDUCE SPACE CONDITIONING DURING NON-WORKING HOURS |
Savings: $17 Cost: - |
- | - | - | - | $17 | 2 | - | - | - | - | - | - |
- - kWh |
- - kW-months/year |
$17 2 MMBtu |
- - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $30,960 Cost: $129,113 |
$26,744 | 310,978 | $3,229 | 701 | $17 | 2 | $290 | - | $171 | - | $509 | - | $26,744 310,978 kWh |
$3,229 701 kW-months/year |
$17 2 MMBtu |
$290 - $ |
$171 - $ |
$509 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: - Cost: - |
- | - | - | - | - | - | - | - | - | - | - | - | - - kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | $ | $ | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | Administrative Changes | Ancillary Material Cost | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | Administrative Changes | Ancillary Material Cost |