Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of Illinois, Chicago
Assessment Year 2019
Principal Product Food Processing, Meatballs and Steaks
NAICS 333241 - Food Product Machinery Manufacturing
SIC 2011 - Meat Packing Plants
Sales $100,000,000-$500,000,000
# of Employees 250
Plant Area (Sq.Ft.) 300,000
Annual Production 40,000,000 Pounds
Production Hrs. Annual 6,257
Location (State) IL
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $1,209,432 23,002,995 kWh $0.05
Electricity Demand $304,106 47,665 kW-months/year $6.38
Electricity Fees $197,819 - $ -
Natural Gas $381,616 92,241 MMBtu $4.14
TOTAL ENERGY COSTS $2,249,847
RECOMMENDED SAVINGS* $114,721 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* -
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Natural Gas Water Usage Electricity Usage Electricity Demand Natural Gas Water Usage
$ kWh $ kW-months/year $ MMBtu $ Tgal
01: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$33,997
Cost:
$8,799
$26,547 504,704 $7,450 996 - - - - $26,547
504,704
kWh
$7,450
996
kW-months/year
-
-
MMBtu
-
-
Tgal
02: 3.4156 USE FLOW CONTROL VALVES ON EQUIPMENT TO OPTIMIZE WATER USE Savings:
$63,690
Cost:
$6,300
- - - - $19,192 4,639 $44,498 5,569 -
-
kWh
-
-
kW-months/year
$19,192
4,639
MMBtu
$44,498
5,569
Tgal
03: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM Savings:
$10,151
Cost:
$14,700
$6,404 121,799 $3,748 501 - - - - $6,404
121,799
kWh
$3,748
501
kW-months/year
-
-
MMBtu
-
-
Tgal
04: 2.2414 USE WASTE HEAT FROM HOT FLUE GASES TO PREHEAT Savings:
$6,883
Cost:
$8,244
- - - - $6,883 1,684 - - -
-
kWh
-
-
kW-months/year
$6,883
1,684
MMBtu
-
-
Tgal
TOTAL RECOMMENDED Savings:
$114,721
Cost:
$38,043
$32,951 626,503 $11,198 1,497 $26,075 6,323 $44,498 5,569 $32,951
626,503
kWh
$11,198
1,497
kW-months/year
$26,075
6,323
MMBtu
$44,498
5,569
Tgal
TOTAL IMPLEMENTED Savings:
-
Cost:
-
- - - - - - - - -
-
kWh
-
-
kW-months/year
-
-
MMBtu
-
-
Tgal
Savings
Cost
$ kWh $ kW-months/year $ MMBtu $ Tgal
Electricity Usage Electricity Demand Natural Gas Water Usage Electricity Usage Electricity Demand Natural Gas Water Usage