Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center Indiana University-Purdue University
Assessment Year 2017
Principal Product Fulfillment Center
NAICS 493110 - General Warehousing and Storage
SIC 4225 - General Warehousing And Storage
Sales $10,000,000-$50,000,000
# of Employees 375
Plant Area (Sq.Ft.) 748,000
Annual Production 64,000,000 Units
Production Hrs. Annual 6,000
Location (State) IN
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $252,595 5,456,250 kWh $0.05
Electricity Demand $192,716 11,349 kW-months/year $16.98
Electricity Fees $17,103 - $ -
Natural Gas $100,100 17,329 MMBtu $5.78
TOTAL ENERGY COSTS $562,514
RECOMMENDED SAVINGS* $80,038 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $77,021
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Natural Gas Electricity Usage Electricity Demand Natural Gas
$ kWh $ kW-months/year $ MMBtu
01: 2.7221 LOWER TEMPERATURE DURING THE WINTER SEASON AND VICE-VERSA Savings:
$21,777
Cost:
$64
$3,767 81,386 - - $18,010 3,116 $3,767
81,386
kWh
-
-
kW-months/year
$18,010
3,116
MMBtu
02: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED Savings:
$2,005
Cost:
$11
$1,033 22,310 $972 57 - - $1,033
22,310
kWh
$972
57
kW-months/year
-
-
MMBtu
03: 2.6211 CONSERVE ENERGY BY EFFICIENT USE OF VENDING MACHINES Savings:
$714
Cost:
-
$475 10,271 $239 14 - - $475
10,271
kWh
$239
14
kW-months/year
-
-
MMBtu
04: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$40,350
Cost:
$48,658
$22,380 483,465 $17,970 1,058 - - $22,380
483,465
kWh
$17,970
1,058
kW-months/year
-
-
MMBtu
05: 2.7241 INSTALL OUTSIDE AIR DAMPER / ECONOMIZER ON HVAC UNIT Savings:
$4,833
Cost:
$11,638
$4,833 104,413 - - - - $4,833
104,413
kWh
-
-
kW-months/year
-
-
MMBtu
06: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$42
Cost:
$84
$28 613 $14 1 - - $28
613
kWh
$14
1
kW-months/year
-
-
MMBtu
07: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE Savings:
$298
Cost:
$1,465
$298 6,445 - - - - $298
6,445
kWh
-
-
kW-months/year
-
-
MMBtu
08: 2.2622 REPLACE EXISTING CHILLER WITH HIGH EFFICIENCY MODEL Savings:
$10,019
Cost:
$47,182
$955 20,641 $944 56 $8,120 1,405 $955
20,641
kWh
$944
56
kW-months/year
$8,120
1,405
MMBtu
TOTAL RECOMMENDED Savings:
$80,038
Cost:
$109,102
$33,769 729,544 $20,139 1,186 $26,130 4,521 $33,769
729,544
kWh
$20,139
1,186
kW-months/year
$26,130
4,521
MMBtu
TOTAL IMPLEMENTED Savings:
$77,021
Cost:
$107,626
$31,963 690,518 $18,928 1,114 $26,130 4,521 $31,963
690,518
kWh
$18,928
1,114
kW-months/year
$26,130
4,521
MMBtu
Savings
Cost
$ kWh $ kW-months/year $ MMBtu
Electricity Usage Electricity Demand Natural Gas Electricity Usage Electricity Demand Natural Gas