Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Univ. of Kansas |
---|---|
Assessment Year | 1983 |
Principal Product | CUSTOM CABINETS |
NAICS | n/a |
SIC | 2434 - Wood Kitchen Cabinets |
Sales | $500,000-$1,000,000 |
# of Employees | 22 |
Plant Area (Sq.Ft.) | 0 |
Annual Production | 1,000 Pieces |
Production Hrs. Annual | 2,074 |
Location (State) | KS |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $32,717 | 429,367 | kWh | $0.08 |
Natural Gas | $8,488 | 1,668 | MMBtu | $5.09 |
Other Energy | $5,664 | 563 | MMBtu | $10.06 |
TOTAL ENERGY COSTS | $46,869 | |||
RECOMMENDED SAVINGS* | $12,067 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $10,512 |
#|Description |
Savings Cost |
Status | Electricity Usage | Natural Gas | Other Energy | Administrative Changes | Electricity Usage | Natural Gas | Other Energy | Administrative Changes | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | MMBtu | $ | MMBtu | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 3.6123 BURN WOOD BY-PRODUCTS FOR HEAT |
Savings: $7,703 Cost: $10,000 |
- | - | $5,903 | 806 | - | - | $1,800 | - |
- - kWh |
$5,903 806 MMBtu |
- - MMBtu |
$1,800 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.2532 USE ONLY AMOUNT OF AIR NECESSARY TO PREVENT EXPLOSION HAZARD |
Savings: $931 Cost: $1,100 |
- | - | $931 | 183 | - | - | - | - |
- - kWh |
$931 183 MMBtu |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.1123 INSTALL AUTOMATIC STACK DAMPER |
Savings: $372 Cost: $300 |
- | - | $372 | 73 | - | - | - | - |
- - kWh |
$372 73 MMBtu |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $223 Cost: $56 |
$223 | 2,931 | - | - | - | - | - | - |
$223 2,931 kWh |
- - MMBtu |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.8226 INCREASE EFFICIENCY OF TRUCKS |
Savings: $171 Cost: $600 |
- | - | - | - | $171 | 17 | - | - |
- - kWh |
- - MMBtu |
$171 17 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.1233 ANALYZE FLUE GAS FOR PROPER AIR/FUEL RATIO |
Savings: $565 Cost: $210 |
- | - | $565 | 111 | - | - | - | - |
- - kWh |
$565 111 MMBtu |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $402 Cost: - |
$402 | 5,275 | - | - | - | - | - | - |
$402 5,275 kWh |
- - MMBtu |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS |
Savings: $156 Cost: $150 |
$156 | 2,052 | - | - | - | - | - | - |
$156 2,052 kWh |
- - MMBtu |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $1,228 Cost: $1,389 |
$1,228 | 16,120 | - | - | - | - | - | - |
$1,228 16,120 kWh |
- - MMBtu |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.7441 REPLACE BROKEN WINDOWS AND/OR WINDOW SASH |
Savings: $275 Cost: $65 |
- | - | $275 | 54 | - | - | - | - |
- - kWh |
$275 54 MMBtu |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
11: 2.6121 REDUCE HOT WATER TEMPERATURE TO THE MINIMUM REQUIRED |
Savings: $41 Cost: - |
- | - | $41 | 8 | - | - | - | - |
- - kWh |
$41 8 MMBtu |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $12,067 Cost: $13,870 |
$2,009 | 26,378 | $8,087 | 1,235 | $171 | 17 | $1,800 | - | $2,009 26,378 kWh |
$8,087 1,235 MMBtu |
$171 17 MMBtu |
$1,800 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $10,512 Cost: $11,731 |
$625 | 8,206 | $8,087 | 1,235 | - | - | $1,800 | - | $625 8,206 kWh |
$8,087 1,235 MMBtu |
- - MMBtu |
$1,800 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | MMBtu | $ | MMBtu | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Natural Gas | Other Energy | Administrative Changes | Electricity Usage | Natural Gas | Other Energy | Administrative Changes |