Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center Univ. of Kansas
Assessment Year 1988
Principal Product LAUNDRY STARCH
NAICS n/a
SIC 2842 - Polishes And Sanitation Goods
Sales $10,000,000-$50,000,000
# of Employees 65
Plant Area (Sq.Ft.) 0
Annual Production 2,500,000 Pieces
Production Hrs. Annual 2,125
Location (State) MO
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $73,779 706,331 kWh $0.10
Natural Gas $74,955 18,497 MMBtu $4.05
TOTAL ENERGY COSTS $148,734
RECOMMENDED SAVINGS* $16,588 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $12,530
#|Description Savings
Cost
Status Electricity Usage Natural Gas Administrative Changes Electricity Usage Natural Gas Administrative Changes
$ kWh $ MMBtu $ $
01: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$7,528
Cost:
$8,010
$7,528 72,098 - - - - $7,528
72,098
kWh
-
-
MMBtu
-
-
$
02: 2.2444 USE HOT PROCESS FLUIDS TO PREHEAT INCOMING PROCESS FLUIDS Savings:
$3,098
Cost:
$500
- - $3,098 765 - - -
-
kWh
$3,098
765
MMBtu
-
-
$
03: 2.2414 USE WASTE HEAT FROM HOT FLUE GASES TO PREHEAT Savings:
$2,831
Cost:
$4,000
- - $2,831 699 - - -
-
kWh
$2,831
699
MMBtu
-
-
$
04: 2.1131 REPAIR FAULTY INSULATION IN FURNACES, BOILERS, ETC Savings:
$563
Cost:
$936
- - $563 139 - - -
-
kWh
$563
139
MMBtu
-
-
$
05: 2.2449 RECOVER HEAT FROM EXHAUSTED STEAM, HOT AIR OR HOT WATER Savings:
$664
Cost:
$800
- - $178 44 $486 - -
-
kWh
$178
44
MMBtu
$486
-
$
06: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS Savings:
$153
Cost:
-
$153 1,465 - - - - $153
1,465
kWh
-
-
MMBtu
-
-
$
07: 2.4312 IMPROVE LUBRICATION PRACTICES Savings:
$153
Cost:
-
$153 1,465 - - - - $153
1,465
kWh
-
-
MMBtu
-
-
$
08: 2.7441 REPLACE BROKEN WINDOWS AND/OR WINDOW SASH Savings:
$1,598
Cost:
$28
$31 293 $1,567 387 - - $31
293
kWh
$1,567
387
MMBtu
-
-
$
TOTAL RECOMMENDED Savings:
$16,588
Cost:
$14,274
$7,865 75,321 $8,237 2,034 $486 - $7,865
75,321
kWh
$8,237
2,034
MMBtu
$486
-
$
TOTAL IMPLEMENTED Savings:
$12,530
Cost:
$8,538
$7,865 75,321 $4,665 1,152 - - $7,865
75,321
kWh
$4,665
1,152
MMBtu
-
-
$
Savings
Cost
$ kWh $ MMBtu $ $
Electricity Usage Natural Gas Administrative Changes Electricity Usage Natural Gas Administrative Changes