Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Lehigh University |
---|---|
Assessment Year | 2014 |
Principal Product | Laminated Windows and Window Frames |
NAICS | 327215 - Glass Product Manufacturing Made of Purchased Glass |
SIC | 3231 - Products Of Purchased Glass |
Sales | $10,000,000-$50,000,000 |
# of Employees | 94 |
Plant Area (Sq.Ft.) | 103,000 |
Annual Production | 105,000 Pieces |
Production Hrs. Annual | 2,080 |
Location (State) | PA |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $297,456 | 4,234,050 | kWh | $0.07 |
Electricity Demand | $22,237 | 10,730 | kW-months/year | $2.07 |
Electricity Fees | $38,069 | - | $ | - |
Natural Gas | $20,012 | 1,957 | MMBtu | $10.23 |
TOTAL ENERGY COSTS | $377,774 | |||
RECOMMENDED SAVINGS* | $42,448 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | - |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes | Ancillary Material Cost | Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes | Ancillary Material Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.8114 CHANGE RATE SCHEDULES OR OTHER CHANGES IN UTILITY SERVICE |
Savings: $6,302 Cost: - |
- | - | - | - | - | - | $6,302 | - | - | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
$6,302 - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $11,973 Cost: $1,000 |
$11,083 | 158,331 | $890 | 430 | - | - | - | - | - | - |
$11,083 158,331 kWh |
$890 430 kW-months/year |
- - MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS |
Savings: $794 Cost: $450 |
$662 | 9,450 | $132 | 64 | - | - | - | - | - | - |
$662 9,450 kWh |
$132 64 kW-months/year |
- - MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7261 INSTALL TIMERS AND/OR THERMOSTATS |
Savings: $2,600 Cost: $2,185 |
- | - | - | - | $2,600 | 254 | - | - | - | - |
- - kWh |
- - kW-months/year |
$2,600 254 MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $439 Cost: $550 |
$375 | 5,350 | $64 | 31 | - | - | - | - | - | - |
$375 5,350 kWh |
$64 31 kW-months/year |
- - MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $7,522 Cost: $9,700 |
$7,228 | 103,251 | $294 | 142 | - | - | - | - | - | - |
$7,228 103,251 kWh |
$294 142 kW-months/year |
- - MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $7,827 Cost: $20,628 |
$6,547 | 93,533 | $1,014 | 490 | - | - | - | - | $266 | - |
$6,547 93,533 kWh |
$1,014 490 kW-months/year |
- - MMBtu |
- - $ |
$266 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.4225 INSTALL COMMON HEADER ON COMPRESSORS |
Savings: $2,849 Cost: $10,313 |
$2,737 | 39,102 | $112 | 54 | - | - | - | - | - | - |
$2,737 39,102 kWh |
$112 54 kW-months/year |
- - MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $2,142 Cost: $8,160 |
$1,386 | 19,802 | $236 | 114 | - | - | - | - | $520 | - |
$1,386 19,802 kWh |
$236 114 kW-months/year |
- - MMBtu |
- - $ |
$520 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $42,448 Cost: $52,986 |
$30,018 | 428,819 | $2,742 | 1,325 | $2,600 | 254 | $6,302 | - | $786 | - | $30,018 428,819 kWh |
$2,742 1,325 kW-months/year |
$2,600 254 MMBtu |
$6,302 - $ |
$786 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: - Cost: - |
- | - | - | - | - | - | - | - | - | - | - - kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes | Ancillary Material Cost | Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes | Ancillary Material Cost |