Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Lehigh University |
---|---|
Assessment Year | 2019 |
Principal Product | Large Forgings |
NAICS | 332111 - Iron and Steel Forging |
SIC | 3462 - Iron And Steel Forgings |
Sales | $100,000,000-$500,000,000 |
# of Employees | 50 |
Plant Area (Sq.Ft.) | 1,000,000 |
Annual Production | 100,000 Units |
Production Hrs. Annual | 6,000 |
Location (State) | PA |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $1,254,618 | 21,089,175 | kWh | $0.06 |
Electricity Demand | $23,981 | 71,333 | kW-months/year | $0.34 |
Electricity Fees | $83,165 | - | $ | - |
Natural Gas | $2,113,317 | 588,063 | MMBtu | $3.59 |
TOTAL ENERGY COSTS | $3,475,081 | |||
RECOMMENDED SAVINGS* | $995,033 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $874,896 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Electricity Usage | Electricity Demand | Natural Gas | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.6212 TURN OFF EQUIPMENT DURING BREAKS, REDUCE OPERATING TIME |
Savings: $106,181 Cost: - |
$104,696 | 1,774,500 | $1,485 | 4,368 | - | - |
$104,696 1,774,500 kWh |
$1,485 4,368 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.1311 REPLACE ELECTRICALLY-OPERATED EQUIPMENT WITH FOSSIL FUEL EQUIPMENT |
Savings: $76,637 Cost: $55,000 |
$98,755 | 1,673,818 | $664 | 1,954 | $(-22,782) | (-6,346) |
$98,755 1,673,818 kWh |
$664 1,954 kW-months/year |
$(-22,782) (-6,346) MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $13,956 Cost: $35,000 |
$13,864 | 234,990 | $91 | 269 | - | - |
$13,864 234,990 kWh |
$91 269 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $58,375 Cost: $186,863 |
$57,705 | 978,048 | $670 | 1,971 | - | - |
$57,705 978,048 kWh |
$670 1,971 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7232 REPLACE EXISTING HVAC UNIT WITH HIGH EFFICIENCY MODEL |
Savings: $12,988 Cost: $50,000 |
$12,886 | 218,400 | $102 | 300 | - | - |
$12,886 218,400 kWh |
$102 300 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7233 USE PROPERLY DESIGNED AND SIZED HVAC EQUIPMENT |
Savings: $726,896 Cost: $16,000,000 |
- | - | - | - | $726,896 | 202,478 |
- - kWh |
- - kW-months/year |
$726,896 202,478 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $995,033 Cost: $16,326,863 |
$287,906 | 4,879,756 | $3,012 | 8,862 | $704,114 | 196,132 | $287,906 4,879,756 kWh |
$3,012 8,862 kW-months/year |
$704,114 196,132 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $874,896 Cost: $16,291,863 |
$169,346 | 2,870,266 | $1,436 | 4,225 | $704,114 | 196,132 | $169,346 2,870,266 kWh |
$1,436 4,225 kW-months/year |
$704,114 196,132 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Electricity Usage | Electricity Demand | Natural Gas |