Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Lehigh University |
---|---|
Assessment Year | 2020 |
Principal Product | Beverages |
NAICS | 312120 - Breweries |
SIC | 2082 - Malt Beverages |
Sales | $10,000,000-$50,000,000 |
# of Employees | 100 |
Plant Area (Sq.Ft.) | 100,000 |
Annual Production | 4,280 Thousand Gallons |
Production Hrs. Annual | 8,112 |
Location (State) | PA |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $306,970 | 5,059,000 | kWh | $0.06 |
Electricity Demand | $45,576 | 11,438 | kW-months/year | $3.98 |
Electricity Fees | $6,246 | - | $ | - |
Natural Gas | $93,317 | 16,344 | MMBtu | $5.71 |
TOTAL ENERGY COSTS | $452,109 | |||
RECOMMENDED SAVINGS* | $42,069 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $23,680 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Electricity Usage | Electricity Demand | Natural Gas | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $1,924 Cost: $40 |
$1,765 | 28,929 | $159 | 40 | - | - |
$1,765 28,929 kWh |
$159 40 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.1311 REPLACE ELECTRICALLY-OPERATED EQUIPMENT WITH FOSSIL FUEL EQUIPMENT |
Savings: $4,376 Cost: $10,000 |
$5,481 | 89,856 | $1,030 | 259 | $(-2,135) | (-374) |
$5,481 89,856 kWh |
$1,030 259 kW-months/year |
$(-2,135) (-374) MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.2449 RECOVER HEAT FROM EXHAUSTED STEAM, HOT AIR OR HOT WATER |
Savings: $5,008 Cost: $12,000 |
- | - | - | - | $5,008 | 877 |
- - kWh |
- - kW-months/year |
$5,008 877 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT |
Savings: $1,370 Cost: $4,000 |
- | - | - | - | $1,370 | 240 |
- - kWh |
- - kW-months/year |
$1,370 240 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $1,681 Cost: $5,750 |
$1,534 | 25,147 | $147 | 37 | - | - |
$1,534 25,147 kWh |
$147 37 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7232 REPLACE EXISTING HVAC UNIT WITH HIGH EFFICIENCY MODEL |
Savings: $15,572 Cost: $60,000 |
$14,060 | 230,491 | $1,512 | 380 | - | - |
$14,060 230,491 kWh |
$1,512 380 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.2442 PREHEAT COMBUSTION AIR WITH WASTE HEAT |
Savings: $9,005 Cost: $35,000 |
- | - | - | - | $9,005 | 1,577 |
- - kWh |
- - kW-months/year |
$9,005 1,577 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7232 REPLACE EXISTING HVAC UNIT WITH HIGH EFFICIENCY MODEL |
Savings: $3,133 Cost: $15,000 |
$2,655 | 43,520 | $478 | 120 | - | - |
$2,655 43,520 kWh |
$478 120 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $42,069 Cost: $141,790 |
$25,495 | 417,943 | $3,326 | 836 | $13,248 | 2,320 | $25,495 417,943 kWh |
$3,326 836 kW-months/year |
$13,248 2,320 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $23,680 Cost: $84,790 |
$20,014 | 328,087 | $2,296 | 577 | $1,370 | 240 | $20,014 328,087 kWh |
$2,296 577 kW-months/year |
$1,370 240 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Electricity Usage | Electricity Demand | Natural Gas |