IAC logo
IAC Assessment: LE0553
Sponsored by:
DOE MESC
IAC logo
IAC Assessment: LE0553
Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center Lehigh University
Assessment Year 2023
Principal Product Plastic sewer pipe
NAICS 326122 - Plastics Pipe and Pipe Fitting Manufacturing
SIC 3084 - Plastics Pipe
Sales $100,000,000-$500,000,000
# of Employees 65
Plant Area (Sq.Ft.) 22,000
Annual Production 15,000,000 Pounds
Production Hrs. Annual 8,736
Location (State) PA
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $419,920 8,388,913 kWh $0.05
Electricity Demand $81,447 14,954 kW-months/year $5.45
Electricity Fees $15,821 - $ -
LPG $12,400 1,031 MMBtu $12.03
TOTAL ENERGY COSTS $529,588
RECOMMENDED SAVINGS* $51,175 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* -
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Ancillary Material Cost Electricity Usage Electricity Demand Ancillary Material Cost
$ kWh $ kW-months/year $ $
01: 2.2511 INSULATE BARE EQUIPMENT Savings:
$547
Cost:
$270
$416 8,320 $131 24 - - $416
8,320
kWh
$131
24
kW-months/year
-
-
$
02: 2.2511 INSULATE BARE EQUIPMENT Savings:
$561
Cost:
$416
$554 11,058 $7 1 - - $554
11,058
kWh
$7
1
kW-months/year
-
-
$
03: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM Savings:
$21,093
Cost:
$22,500
$18,346 336,912 $2,747 504 - - $18,346
336,912
kWh
$2,747
504
kW-months/year
-
-
$
04: 2.2628 UTILIZE A LESS EXPENSIVE COOLING METHOD Savings:
$8,974
Cost:
$40,000
$7,862 157,248 $1,112 204 - - $7,862
157,248
kWh
$1,112
204
kW-months/year
-
-
$
05: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS Savings:
$20,000
Cost:
$91,800
- - - - $20,000 - -
-
kWh
-
-
kW-months/year
$20,000
-
$
TOTAL RECOMMENDED Savings:
$51,175
Cost:
$154,986
$27,178 513,538 $3,997 733 $20,000 - $27,178
513,538
kWh
$3,997
733
kW-months/year
$20,000
-
$
TOTAL IMPLEMENTED Savings:
-
Cost:
-
- - - - - - -
-
kWh
-
-
kW-months/year
-
-
$
Savings
Cost
$ kWh $ kW-months/year $ $
Electricity Usage Electricity Demand Ancillary Material Cost Electricity Usage Electricity Demand Ancillary Material Cost