IAC logo
IAC Assessment: LE0563
Sponsored by:
DOE MESC
IAC logo
IAC Assessment: LE0563
Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center Lehigh University
Assessment Year 2024
Principal Product Custom stone kitchen & bath products
NAICS 423320 - Brick, Stone, and Related Construction Material Merchant Wholesalers
SIC 5032 - Brick, Stone, & Related Materials
Sales $1,000,000-$5,000,000
# of Employees 87
Plant Area (Sq.Ft.) 100,000
Annual Production 7,000 Units
Production Hrs. Annual 3,120
Location (State) PA
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $58,698 757,800 kWh $0.08
Electricity Demand $9,282 2,376 kW-months/year $3.91
Electricity Fees $13,607 - $ -
Natural Gas $8,225 680 MMBtu $12.10
Fuel Oil #2 $439,715 16,119 MMBtu $27.28
TOTAL ENERGY COSTS $529,527
RECOMMENDED SAVINGS* $31,171 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* -
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Natural Gas Electricity Usage Electricity Demand Natural Gas
$ kWh $ kW-months/year $ MMBtu
01: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED Savings:
$474
Cost:
$100
$396 5,148 $78 20 - - $396
5,148
kWh
$78
20
kW-months/year
-
-
MMBtu
02: 2.7261 INSTALL TIMERS AND/OR THERMOSTATS Savings:
$2,648
Cost:
$960
$2,624 34,075 - - $24 2 $2,624
34,075
kWh
-
-
kW-months/year
$24
2
MMBtu
03: 2.7135 INSTALL OCCUPANCY SENSORS Savings:
$307
Cost:
$140
$307 3,991 - - - - $307
3,991
kWh
-
-
kW-months/year
-
-
MMBtu
04: 2.2443 RE-USE OR RECYCLE HOT OR COLD PROCESS EXHAUST AIR Savings:
$5,106
Cost:
$2,500
- - - - $5,106 422 -
-
kWh
-
-
kW-months/year
$5,106
422
MMBtu
05: 2.7232 REPLACE EXISTING HVAC UNIT WITH HIGH EFFICIENCY MODEL Savings:
$14,800
Cost:
$19,440
- - - - $14,800 1,223 -
-
kWh
-
-
kW-months/year
$14,800
1,223
MMBtu
06: 2.7232 REPLACE EXISTING HVAC UNIT WITH HIGH EFFICIENCY MODEL Savings:
$6,361
Cost:
$21,000
$6,189 80,371 $172 44 - - $6,189
80,371
kWh
$172
44
kW-months/year
-
-
MMBtu
07: 2.7312 MINIMIZE USE OF OUTSIDE MAKE-UP AIR FOR VENTILATION EXCEPT WHEN USED FOR ECONOMIZER CYCLE Savings:
$1,253
Cost:
$9,000
$(-358) (-4,653) $(-35) (-9) $1,646 136 $(-358)
(-4,653)
kWh
$(-35)
(-9)
kW-months/year
$1,646
136
MMBtu
08: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$222
Cost:
$1,600
$179 2,330 $43 11 - - $179
2,330
kWh
$43
11
kW-months/year
-
-
MMBtu
TOTAL RECOMMENDED Savings:
$31,171
Cost:
$54,740
$9,337 121,262 $258 66 $21,576 1,783 $9,337
121,262
kWh
$258
66
kW-months/year
$21,576
1,783
MMBtu
TOTAL IMPLEMENTED Savings:
-
Cost:
-
- - - - - - -
-
kWh
-
-
kW-months/year
-
-
MMBtu
Savings
Cost
$ kWh $ kW-months/year $ MMBtu
Electricity Usage Electricity Demand Natural Gas Electricity Usage Electricity Demand Natural Gas