Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center Lehigh University
Assessment Year 2025
Principal Product collagen casing
NAICS 311612 - Meat Processed from Carcasses
SIC 2013 - Sausages And Other Prepared Meats
Sales $100,000,000-$500,000,000
# of Employees 127
Plant Area (Sq.Ft.) 132,142
Annual Production 592,021,000 Units
Production Hrs. Annual 4,368
Location (State) NJ
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $1,454,221 12,362,093 kWh $0.12
Electricity Demand $148,361 23,756 kW-months/year $6.25
Electricity Fees $17,384 - $ -
Natural Gas $675,218 202,404 MMBtu $3.34
TOTAL ENERGY COSTS $2,295,184
RECOMMENDED SAVINGS* $275,777 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* -
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Natural Gas One-time Revenue or Avoided Cost Electricity Usage Electricity Demand Natural Gas One-time Revenue or Avoided Cost
$ kWh $ kW-months/year $ MMBtu $ $
01: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED Savings:
$18,356
Cost:
-
$17,112 145,018 $1,244 199 - - - - $17,112
145,018
kWh
$1,244
199
kW-months/year
-
-
MMBtu
-
-
$
02: 2.7261 INSTALL TIMERS AND/OR THERMOSTATS Savings:
$44,588
Cost:
$1,600
$8,756 74,206 - - $35,832 10,728 - - $8,756
74,206
kWh
-
-
kW-months/year
$35,832
10,728
MMBtu
-
-
$
03: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$12,225
Cost:
$3,680
$11,393 96,575 $832 133 - - - - $11,393
96,575
kWh
$832
133
kW-months/year
-
-
MMBtu
-
-
$
04: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$55,828
Cost:
$52,000
$52,053 441,110 $3,775 604 - - - - $52,053
441,110
kWh
$3,775
604
kW-months/year
-
-
MMBtu
-
-
$
05: 2.2614 USE COOLING TOWER OR ECONOMIZER TO REPLACE CHILLER COOLING Savings:
$18,412
Cost:
$23,182
$17,163 145,452 $1,249 200 - - - - $17,163
145,452
kWh
$1,249
200
kW-months/year
-
-
MMBtu
-
-
$
06: 2.7135 INSTALL OCCUPANCY SENSORS Savings:
$636
Cost:
$1,081
$636 5,385 - - - - - - $636
5,385
kWh
-
-
kW-months/year
-
-
MMBtu
-
-
$
07: 2.9114 USE SOLAR HEAT TO MAKE ELECTRICTY Savings:
$72,625
Cost:
$210,000
$39,325 333,252 - - - - $33,300 - $39,325
333,252
kWh
-
-
kW-months/year
-
-
MMBtu
$33,300
-
$
08: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$12,248
Cost:
$44,740
$10,360 87,799 $1,888 302 - - - - $10,360
87,799
kWh
$1,888
302
kW-months/year
-
-
MMBtu
-
-
$
09: 2.7232 REPLACE EXISTING HVAC UNIT WITH HIGH EFFICIENCY MODEL Savings:
$40,859
Cost:
$167,895
$38,090 322,795 $2,769 443 - - - - $38,090
322,795
kWh
$2,769
443
kW-months/year
-
-
MMBtu
-
-
$
TOTAL RECOMMENDED Savings:
$275,777
Cost:
$504,178
$194,888 1,651,592 $11,757 1,881 $35,832 10,728 $33,300 - $194,888
1,651,592
kWh
$11,757
1,881
kW-months/year
$35,832
10,728
MMBtu
$33,300
-
$
TOTAL IMPLEMENTED Savings:
-
Cost:
-
- - - - - - - - -
-
kWh
-
-
kW-months/year
-
-
MMBtu
-
-
$
Savings
Cost
$ kWh $ kW-months/year $ MMBtu $ $
Electricity Usage Electricity Demand Natural Gas One-time Revenue or Avoided Cost Electricity Usage Electricity Demand Natural Gas One-time Revenue or Avoided Cost