Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Massachusetts |
---|---|
Assessment Year | 1985 |
Principal Product | SAFETY EQUIPMENT |
NAICS | n/a |
SIC | 3842 - Surgical Appliances And Supplies |
Sales | $10,000,000-$50,000,000 |
# of Employees | 280 |
Plant Area (Sq.Ft.) | 0 |
Annual Production | 6,000,000 Pounds |
Production Hrs. Annual | 6,000 |
Location (State) | RI |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $358,880 | 4,607,269 | kWh | $0.08 |
Fuel Oil #2 | $11,029 | 1,547 | MMBtu | $7.13 |
Fuel Oil #6 | $79,654 | 13,201 | MMBtu | $6.03 |
TOTAL ENERGY COSTS | $449,563 | |||
RECOMMENDED SAVINGS* | $31,396 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $17,503 |
#|Description |
Savings Cost |
Status | Electricity Usage | Fuel Oil #2 | Fuel Oil #6 | Administrative Changes | Electricity Usage | Fuel Oil #2 | Fuel Oil #6 | Administrative Changes | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | MMBtu | $ | MMBtu | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $3,470 Cost: $452 |
$3,470 | 44,549 | - | - | - | - | - | - |
$3,470 44,549 kWh |
- - MMBtu |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.1233 ANALYZE FLUE GAS FOR PROPER AIR/FUEL RATIO |
Savings: $977 Cost: $1,500 |
- | - | $1,265 | 177 | - | - | $(-288) | - |
- - kWh |
$1,265 177 MMBtu |
- - MMBtu |
$(-288) - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS |
Savings: $1,228 Cost: $400 |
$1,228 | 15,826 | - | - | - | - | - | - |
$1,228 15,826 kWh |
- - MMBtu |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4322 USE OR REPLACE WITH ENERGY EFFICIENT SUBSTITUTES |
Savings: $6,309 Cost: $11,314 |
$6,309 | 80,891 | - | - | - | - | - | - |
$6,309 80,891 kWh |
- - MMBtu |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7226 USE COMPUTER PROGRAMS TO OPTIMIZE HVAC PERFORMANCE |
Savings: $1,730 Cost: $400 |
$2,671 | 34,291 | - | - | $(-941) | (-156) | - | - |
$2,671 34,291 kWh |
- - MMBtu |
$(-941) (-156) MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.2113 REPAIR OR REPLACE STEAM TRAPS |
Savings: $3,789 Cost: $533 |
- | - | - | - | $5,489 | 910 | $(-1,700) | - |
- - kWh |
- - MMBtu |
$5,489 910 MMBtu |
$(-1,700) - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT |
Savings: $13,893 Cost: $27,500 |
- | - | - | - | $13,893 | 2,304 | - | - |
- - kWh |
- - MMBtu |
$13,893 2,304 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $31,396 Cost: $42,099 |
$13,678 | 175,557 | $1,265 | 177 | $18,441 | 3,058 | $(-1,988) | - | $13,678 175,557 kWh |
$1,265 177 MMBtu |
$18,441 3,058 MMBtu |
$(-1,988) - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $17,503 Cost: $14,599 |
$13,678 | 175,557 | $1,265 | 177 | $4,548 | 754 | $(-1,988) | - | $13,678 175,557 kWh |
$1,265 177 MMBtu |
$4,548 754 MMBtu |
$(-1,988) - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | MMBtu | $ | MMBtu | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Fuel Oil #2 | Fuel Oil #6 | Administrative Changes | Electricity Usage | Fuel Oil #2 | Fuel Oil #6 | Administrative Changes |