Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Massachusetts |
---|---|
Assessment Year | 2002 |
Principal Product | Corrugated paper |
NAICS | n/a |
SIC | 2653 - Corrugated And Solid Fiber Boxes |
Sales | $10,000,000-$50,000,000 |
# of Employees | 150 |
Plant Area (Sq.Ft.) | 250,000 |
Annual Production | 36,000 Tons |
Production Hrs. Annual | 8,568 |
Location (State) | MA |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $1,393,058 | 20,056,800 | kWh | $0.07 |
Electricity Demand | $169,356 | 35,327 | kW-months/year | $4.79 |
Electricity Fees | $(-540) | - | $ | - |
Natural Gas | $1,086,548 | 232,103 | MMBtu | $4.68 |
TOTAL ENERGY COSTS | $2,701,110 | |||
RECOMMENDED SAVINGS* | $1,161,166 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $3,709 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Water Disposal | Electricity Usage | Electricity Demand | Natural Gas | Water Disposal | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | Tgal | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 3.4151 MINIMIZE WATER USAGE |
Savings: $32,733 Cost: $25,000 |
$2,240 | 31,959 | - | - | $17,778 | 3,643 | $12,715 | 4,915,600 |
$2,240 31,959 kWh |
- - kW-months/year |
$17,778 3,643 MMBtu |
$12,715 4,915,600 Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT |
Savings: $161,660 Cost: $225,500 |
- | - | - | - | $161,660 | 33,127 | - | - |
- - kWh |
- - kW-months/year |
$161,660 33,127 MMBtu |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.1233 ANALYZE FLUE GAS FOR PROPER AIR/FUEL RATIO |
Savings: $59,990 Cost: $26,000 |
- | - | - | - | $59,990 | 12,293 | - | - |
- - kWh |
- - kW-months/year |
$59,990 12,293 MMBtu |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $23,884 Cost: $20,000 |
$23,884 | 340,837 | - | - | - | - | - | - |
$23,884 340,837 kWh |
- - kW-months/year |
- - MMBtu |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 3.4111 USE CLOSED CYCLE PROCESS TO MINIMIZE WASTE WATER PRODUCTION |
Savings: $19,687 Cost: $55,000 |
$(-26,874) | 340,837 | - | - | - | - | $46,561 | 16,664,079 |
$(-26,874) 340,837 kWh |
- - kW-months/year |
- - MMBtu |
$46,561 16,664,079 Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $6,163 Cost: $23,000 |
$5,628 | 80,307 | $535 | 112 | - | - | - | - |
$5,628 80,307 kWh |
$535 112 kW-months/year |
- - MMBtu |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.2122 INSTALL / REPAIR INSULATION ON CONDENSATE LINES |
Savings: $3,709 Cost: $1,000 |
- | - | - | - | $3,709 | 760 | - | - |
- - kWh |
- - kW-months/year |
$3,709 760 MMBtu |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $2,677 Cost: $9,000 |
$2,443 | 34,869 | $234 | 49 | - | - | - | - |
$2,443 34,869 kWh |
$234 49 kW-months/year |
- - MMBtu |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.3415 USE A FOSSIL FUEL ENGINE TO COGENERATE ELECTRICITY OR MOTIVE POWER; AND UTILIZE HEAT |
Savings: $850,663 Cost: $3,285,330 |
$979,003 | 19,674,300 | - | - | $(-128,340) | (-80,903) | - | - |
$979,003 19,674,300 kWh |
- - kW-months/year |
$(-128,340) (-80,903) MMBtu |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $1,161,166 Cost: $3,669,830 |
$986,324 | 20,503,109 | $769 | 161 | $114,797 | (-31,080) | $59,276 | 21,579,679 | $986,324 20,503,109 kWh |
$769 161 kW-months/year |
$114,797 (-31,080) MMBtu |
$59,276 21,579,679 Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $3,709 Cost: $1,000 |
- | - | - | - | $3,709 | 760 | - | - | - - kWh |
- - kW-months/year |
$3,709 760 MMBtu |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | Tgal | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Water Disposal | Electricity Usage | Electricity Demand | Natural Gas | Water Disposal |