Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Massachusetts |
---|---|
Assessment Year | 2005 |
Principal Product | plastic auto parts |
NAICS | 339991 - Gasket, Packing, and Sealing Device Manufacturing |
SIC | 3069 - Fabricated Rubber Products, Nec |
Sales | $50,000,000-$100,000,000 |
# of Employees | 560 |
Plant Area (Sq.Ft.) | 300,000 |
Annual Production | 17,000,000 Pieces |
Production Hrs. Annual | 8,520 |
Location (State) | NH |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $1,421,618 | 16,990,642 | kWh | $0.08 |
Electricity Demand | $240,082 | 34,277 | kW-months/year | $7.00 |
Electricity Fees | $11,915 | - | $ | - |
LPG | $148,389 | 12,824 | MMBtu | $11.57 |
TOTAL ENERGY COSTS | $1,822,004 | |||
RECOMMENDED SAVINGS* | $203,937 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $91,824 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | LPG | Electricity Usage | Electricity Demand | LPG | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $98,511 Cost: $312,103 |
$81,197 | 988,277 | $17,314 | 2,470 | - | - |
$81,197 988,277 kWh |
$17,314 2,470 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $37,163 Cost: $86,315 |
$31,623 | 384,900 | $5,540 | 790 | - | - |
$31,623 384,900 kWh |
$5,540 790 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7243 IMPROVE AIR CIRCULATION WITH DESTRATIFICATION FANS / OTHER METHODS |
Savings: $15,630 Cost: $6,540 |
$(-955) | (-11,600) | $(-135) | (-19) | $16,720 | 1,445 |
$(-955) (-11,600) kWh |
$(-135) (-19) kW-months/year |
$16,720 1,445 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $14,153 Cost: - |
$12,545 | 152,700 | $1,608 | 230 | - | - |
$12,545 152,700 kWh |
$1,608 230 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.1311 REPLACE ELECTRICALLY-OPERATED EQUIPMENT WITH FOSSIL FUEL EQUIPMENT |
Savings: $13,602 Cost: $77,760 |
$19,482 | 237,125 | $7,865 | 1,122 | $(-13,745) | (-1,188) |
$19,482 237,125 kWh |
$7,865 1,122 kW-months/year |
$(-13,745) (-1,188) MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS |
Savings: $7,599 Cost: $2,010 |
$6,793 | 82,680 | $806 | 115 | - | - |
$6,793 82,680 kWh |
$806 115 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $6,815 Cost: $7,660 |
$6,000 | 73,044 | $815 | 116 | - | - |
$6,000 73,044 kWh |
$815 116 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.2614 USE COOLING TOWER OR ECONOMIZER TO REPLACE CHILLER COOLING |
Savings: $6,340 Cost: $25,150 |
$6,340 | 77,330 | - | - | - | - |
$6,340 77,330 kWh |
- - kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $2,540 Cost: $800 |
$2,540 | 30,900 | - | - | - | - |
$2,540 30,900 kWh |
- - kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.2443 RE-USE OR RECYCLE HOT OR COLD PROCESS EXHAUST AIR |
Savings: $1,584 Cost: $1,300 |
- | - | - | - | $1,584 | 137 |
- - kWh |
- - kW-months/year |
$1,584 137 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $203,937 Cost: $519,638 |
$165,565 | 2,015,356 | $33,813 | 4,824 | $4,559 | 394 | $165,565 2,015,356 kWh |
$33,813 4,824 kW-months/year |
$4,559 394 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $91,824 Cost: $129,775 |
$64,886 | 789,954 | $8,634 | 1,232 | $18,304 | 1,582 | $64,886 789,954 kWh |
$8,634 1,232 kW-months/year |
$18,304 1,582 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | LPG | Electricity Usage | Electricity Demand | LPG |