Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Massachusetts |
---|---|
Assessment Year | 2013 |
Principal Product | Photochemicals, Radiation Cured Chemicals and Additives |
NAICS | 325199 - All Other Basic Organic Chemical Manufacturing |
SIC | 2869 - Industrial Organic Chemicals, Nec |
Sales | $1,000,000-$5,000,000 |
# of Employees | 40 |
Plant Area (Sq.Ft.) | 37,000 |
Annual Production | 130 Tons |
Production Hrs. Annual | 4,335 |
Location (State) | CT |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $140,800 | 1,292,127 | kWh | $0.11 |
Electricity Demand | $53,203 | 4,498 | kW-months/year | $11.83 |
Electricity Fees | $6,066 | - | $ | - |
Natural Gas | $68,752 | 5,030 | MMBtu | $13.67 |
Fuel Oil #2 | $4,743 | 169 | MMBtu | $28.03 |
TOTAL ENERGY COSTS | $273,564 | |||
RECOMMENDED SAVINGS* | $34,697 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $4,335 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Electricity Usage | Electricity Demand | Natural Gas | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $17,618 Cost: $35,000 |
$17,618 | 167,473 | - | - | - | - |
$17,618 167,473 kWh |
- - kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.1311 REPLACE ELECTRICALLY-OPERATED EQUIPMENT WITH FOSSIL FUEL EQUIPMENT |
Savings: $6,430 Cost: $25,000 |
$7,063 | 67,141 | $2,834 | 211 | $(-3,467) | (-270) |
$7,063 67,141 kWh |
$2,834 211 kW-months/year |
$(-3,467) (-270) MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.2611 MODERATE COOLING TOWER OUTLET TEMPERATURE |
Savings: $6,314 Cost: $14,000 |
$6,314 | 60,021 | - | - | - | - |
$6,314 60,021 kWh |
- - kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.2136 INSTALL / REPAIR INSULATION ON STEAM LINES |
Savings: $2,170 Cost: $2,000 |
- | - | - | - | $2,170 | 169 |
- - kWh |
- - kW-months/year |
$2,170 169 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $2,165 Cost: $4,055 |
$1,601 | 15,215 | $564 | 42 | - | - |
$1,601 15,215 kWh |
$564 42 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $34,697 Cost: $80,055 |
$32,596 | 309,850 | $3,398 | 253 | $(-1,297) | (-101) | $32,596 309,850 kWh |
$3,398 253 kW-months/year |
$(-1,297) (-101) MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $4,335 Cost: $6,055 |
$1,601 | 15,215 | $564 | 42 | $2,170 | 169 | $1,601 15,215 kWh |
$564 42 kW-months/year |
$2,170 169 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||