Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of Massachusetts
Assessment Year 2019
Principal Product Plastic products for mediacl devices
NAICS 326199 - All Other Plastics Product Manufacturing
SIC 3089 - Plastics Products, Nec
Sales $10,000,000-$50,000,000
# of Employees 780
Plant Area (Sq.Ft.) 190,000
Annual Production 120,000 Units
Production Hrs. Annual 8,736
Location (State) MA
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $2,265,262 16,920,400 kWh $0.13
Electricity Demand $167,114 31,892 kW-months/year $5.24
Electricity Fees $(-6,213) - $ -
Natural Gas $128,418 10,564 MMBtu $12.16
TOTAL ENERGY COSTS $2,599,604
RECOMMENDED SAVINGS* $366,656 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $112,694
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Water Disposal One-time Revenue or Avoided Cost Electricity Usage Electricity Demand Water Disposal One-time Revenue or Avoided Cost
$ kWh $ kW-months/year $ Tgal $ $
01: 2.7241 INSTALL OUTSIDE AIR DAMPER / ECONOMIZER ON HVAC UNIT Savings:
$96,513
Cost:
$144,000
$96,513 720,244 - - - - - - $96,513
720,244
kWh
-
-
kW-months/year
-
-
Tgal
-
-
$
02: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$82,405
Cost:
$128,486
$77,380 577,463 $5,025 959 - - - - $77,380
577,463
kWh
$5,025
959
kW-months/year
-
-
Tgal
-
-
$
03: 2.9113 USE SOLAR HEAT FOR HEAT Savings:
$77,280
Cost:
$383,955
$62,315 465,041 - - - - $14,965 - $62,315
465,041
kWh
-
-
kW-months/year
-
-
Tgal
$14,965
-
$
04: 2.2614 USE COOLING TOWER OR ECONOMIZER TO REPLACE CHILLER COOLING Savings:
$40,486
Cost:
$165,914
$40,486 302,135 - - - - - - $40,486
302,135
kWh
-
-
kW-months/year
-
-
Tgal
-
-
$
05: 2.7232 REPLACE EXISTING HVAC UNIT WITH HIGH EFFICIENCY MODEL Savings:
$28,514
Cost:
$32,800
$28,514 212,792 - - - - - - $28,514
212,792
kWh
-
-
kW-months/year
-
-
Tgal
-
-
$
06: 3.4116 METER RECYCLED WATER (TO REDUCE SEWER CHARGES) Savings:
$25,552
Cost:
$7,916
- - - - $25,552 5,110 - - -
-
kWh
-
-
kW-months/year
$25,552
5,110
Tgal
-
-
$
07: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM Savings:
$14,131
Cost:
$5,222
$14,131 105,458 - - - - - - $14,131
105,458
kWh
-
-
kW-months/year
-
-
Tgal
-
-
$
08: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM Savings:
$1,775
Cost:
$200
$1,775 13,247 - - - - - - $1,775
13,247
kWh
-
-
kW-months/year
-
-
Tgal
-
-
$
TOTAL RECOMMENDED Savings:
$366,656
Cost:
$868,493
$321,114 2,396,380 $5,025 959 $25,552 5,110 $14,965 - $321,114
2,396,380
kWh
$5,025
959
kW-months/year
$25,552
5,110
Tgal
$14,965
-
$
TOTAL IMPLEMENTED Savings:
$112,694
Cost:
$161,486
$107,669 803,502 $5,025 959 - - - - $107,669
803,502
kWh
$5,025
959
kW-months/year
-
-
Tgal
-
-
$
Savings
Cost
$ kWh $ kW-months/year $ Tgal $ $
Electricity Usage Electricity Demand Water Disposal One-time Revenue or Avoided Cost Electricity Usage Electricity Demand Water Disposal One-time Revenue or Avoided Cost