IAC logo
IAC Assessment: ME0224
Sponsored by:
DOE MESC
IAC logo
IAC Assessment: ME0224
Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of Maine
Assessment Year 1997
Principal Product Surface Mount Capacitors
NAICS n/a
SIC 3675 - Electronic Capacitors
Sales $10,000,000-$50,000,000
# of Employees 275
Plant Area (Sq.Ft.) 73,000
Annual Production 6,500 Pieces
Production Hrs. Annual 6,250
Location (State) ME
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $392,954 5,822,099 kWh $0.07
Electricity Demand $93,585 11,358 kW-months/year $8.24
Electricity Fees $12,447 - $ -
LPG $267 9 MMBtu $29.67
Fuel Oil #2 $64,384 12,601 MMBtu $5.11
TOTAL ENERGY COSTS $581,327
RECOMMENDED SAVINGS* $77,068 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $68,903
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Fuel Oil #2 Water Disposal Ancillary Material Cost Water Consumption Electricity Usage Electricity Demand Fuel Oil #2 Water Disposal Ancillary Material Cost Water Consumption
$ kWh $ kW-months/year $ MMBtu $ Tgal $ $ $ Tgal
01: 2.1311 REPLACE ELECTRICALLY-OPERATED EQUIPMENT WITH FOSSIL FUEL EQUIPMENT Savings:
$47,583
Cost:
$18,145
$68,924 985,053 - - $(-21,341) (-4,201) - - - - - - $68,924
985,053
kWh
-
-
kW-months/year
$(-21,341)
(-4,201)
MMBtu
-
-
Tgal
-
-
$
-
-
Tgal
02: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS Savings:
$10,674
Cost:
$5,557
$8,693 123,974 $1,981 241 - - - - - - - - $8,693
123,974
kWh
$1,981
241
kW-months/year
-
-
MMBtu
-
-
Tgal
-
-
$
-
-
Tgal
03: 4.6520 REPLACE EXISTING EQUIPMENT WITH MORE SUITABLE SUBSTITUTES Savings:
$4,198
Cost:
$1,666
$5,810 82,943 $444 54 $(-2,056) (-405) - - - - - - $5,810
82,943
kWh
$444
54
kW-months/year
$(-2,056)
(-405)
MMBtu
-
-
Tgal
-
-
$
-
-
Tgal
04: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS Savings:
$3,967
Cost:
$650
$3,967 81,477 - - - - - - - - - - $3,967
81,477
kWh
-
-
kW-months/year
-
-
MMBtu
-
-
Tgal
-
-
$
-
-
Tgal
05: 2.2136 INSTALL / REPAIR INSULATION ON STEAM LINES Savings:
$3,067
Cost:
$279
- - - - $3,067 419 - - - - - - -
-
kWh
-
-
kW-months/year
$3,067
419
MMBtu
-
-
Tgal
-
-
$
-
-
Tgal
06: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$965
Cost:
$250
$965 13,775 - - - - - - - - - - $965
13,775
kWh
-
-
kW-months/year
-
-
MMBtu
-
-
Tgal
-
-
$
-
-
Tgal
07: 4.1130 INSTALL REFRIGERATION SYSTEM TO COOL PRODUCT Savings:
$3,640
Cost:
$5,000
- - - - - - - - $3,640 - - - -
-
kWh
-
-
kW-months/year
-
-
MMBtu
-
-
Tgal
$3,640
-
$
-
-
Tgal
08: 3.4116 METER RECYCLED WATER (TO REDUCE SEWER CHARGES) Savings:
$2,760
Cost:
-
- - - - - - $2,760 - - - - - -
-
kWh
-
-
kW-months/year
-
-
MMBtu
$2,760
-
Tgal
-
-
$
-
-
Tgal
09: 3.4111 USE CLOSED CYCLE PROCESS TO MINIMIZE WASTE WATER PRODUCTION Savings:
$214
Cost:
$1,850
$(-421) (-6,155) $(-203) (-8) - - $641 210,469 - - $197 - $(-421)
(-6,155)
kWh
$(-203)
(-8)
kW-months/year
-
-
MMBtu
$641
210,469
Tgal
-
-
$
$197
-
Tgal
TOTAL RECOMMENDED Savings:
$77,068
Cost:
$33,397
$87,938 1,281,067 $2,222 287 $(-20,330) (-4,187) $3,401 210,469 $3,640 - $197 - $87,938
1,281,067
kWh
$2,222
287
kW-months/year
$(-20,330)
(-4,187)
MMBtu
$3,401
210,469
Tgal
$3,640
-
$
$197
-
Tgal
TOTAL IMPLEMENTED Savings:
$68,903
Cost:
$31,081
$78,161 1,116,647 $1,778 233 $(-18,274) (-3,782) $3,401 210,469 $3,640 - $197 - $78,161
1,116,647
kWh
$1,778
233
kW-months/year
$(-18,274)
(-3,782)
MMBtu
$3,401
210,469
Tgal
$3,640
-
$
$197
-
Tgal
Savings
Cost
$ kWh $ kW-months/year $ MMBtu $ Tgal $ $ $ Tgal
Electricity Usage Electricity Demand Fuel Oil #2 Water Disposal Ancillary Material Cost Water Consumption Electricity Usage Electricity Demand Fuel Oil #2 Water Disposal Ancillary Material Cost Water Consumption