Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Maine |
---|---|
Assessment Year | 2000 |
Principal Product | Auto-reset circuit breakers |
NAICS | n/a |
SIC | 3613 - Switchgear And Switchboard Apparatus |
Sales | $5,000,000-$10,000,000 |
# of Employees | 100 |
Plant Area (Sq.Ft.) | 32,200 |
Annual Production | 53,000,000 Pieces |
Production Hrs. Annual | 6,240 |
Location (State) | ME |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $202,213 | 1,947,245 | kWh | $0.10 |
Electricity Demand | $30,024 | 3,098 | kW-months/year | $9.69 |
LPG | $2,758 | 251 | MMBtu | $10.99 |
Fuel Oil #2 | $5,359 | 1,426 | MMBtu | $3.76 |
TOTAL ENERGY COSTS | $240,354 | |||
RECOMMENDED SAVINGS* | $28,842 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $4,921 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | LPG | Fuel Oil #2 | Solid Waste (non-haz) | Electricity Usage | Electricity Demand | LPG | Fuel Oil #2 | Solid Waste (non-haz) | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | MMBtu | $ | lb | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $11,421 Cost: $18,457 |
$9,403 | 156,800 | $2,018 | 312 | - | - | - | - | - | - |
$9,403 156,800 kWh |
$2,018 312 kW-months/year |
- - MMBtu |
- - MMBtu |
- - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.1311 REPLACE ELECTRICALLY-OPERATED EQUIPMENT WITH FOSSIL FUEL EQUIPMENT |
Savings: $6,142 Cost: $13,995 |
$3,113 | 55,393 | $3,985 | 410 | - | - | $(-956) | (-252) | - | - |
$3,113 55,393 kWh |
$3,985 410 kW-months/year |
- - MMBtu |
$(-956) (-252) MMBtu |
- - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.2511 INSULATE BARE EQUIPMENT |
Savings: $3,630 Cost: $600 |
$3,630 | 34,877 | - | - | - | - | - | - | - | - |
$3,630 34,877 kWh |
- - kW-months/year |
- - MMBtu |
- - MMBtu |
- - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.2136 INSTALL / REPAIR INSULATION ON STEAM LINES |
Savings: $2,217 Cost: $1,515 |
$2,217 | 138,335 | - | - | - | - | - | - | - | - |
$2,217 138,335 kWh |
- - kW-months/year |
- - MMBtu |
- - MMBtu |
- - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.1311 REPLACE ELECTRICALLY-OPERATED EQUIPMENT WITH FOSSIL FUEL EQUIPMENT |
Savings: $1,778 Cost: $800 |
$1,493 | 26,377 | $1,515 | 156 | $(-1,230) | (-112) | - | - | - | - |
$1,493 26,377 kWh |
$1,515 156 kW-months/year |
$(-1,230) (-112) MMBtu |
- - MMBtu |
- - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS |
Savings: $1,450 Cost: $1,500 |
$1,450 | 25,791 | - | - | - | - | - | - | - | - |
$1,450 25,791 kWh |
- - kW-months/year |
- - MMBtu |
- - MMBtu |
- - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.1311 REPLACE ELECTRICALLY-OPERATED EQUIPMENT WITH FOSSIL FUEL EQUIPMENT |
Savings: $1,291 Cost: $750 |
$1,478 | 26,377 | $1,049 | 108 | $(-1,236) | (-113) | - | - | - | - |
$1,478 26,377 kWh |
$1,049 108 kW-months/year |
$(-1,236) (-113) MMBtu |
- - MMBtu |
- - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE |
Savings: $373 Cost: $370 |
$373 | 6,741 | - | - | - | - | - | - | - | - |
$373 6,741 kWh |
- - kW-months/year |
- - MMBtu |
- - MMBtu |
- - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 3.5217 REUSE / RECYCLE/ SELL PAPER PRODUCTS |
Savings: $540 Cost: - |
- | - | - | - | - | - | - | - | $540 | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
- - MMBtu |
$540 - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $28,842 Cost: $37,987 |
$23,157 | 470,691 | $8,567 | 986 | $(-2,466) | (-225) | $(-956) | (-252) | $540 | - | $23,157 470,691 kWh |
$8,567 986 kW-months/year |
$(-2,466) (-225) MMBtu |
$(-956) (-252) MMBtu |
$540 - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $4,921 Cost: $1,350 |
$5,108 | 61,254 | $1,049 | 108 | $(-1,236) | (-113) | - | - | - | - | $5,108 61,254 kWh |
$1,049 108 kW-months/year |
$(-1,236) (-113) MMBtu |
- - MMBtu |
- - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | MMBtu | $ | lb | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | LPG | Fuel Oil #2 | Solid Waste (non-haz) | Electricity Usage | Electricity Demand | LPG | Fuel Oil #2 | Solid Waste (non-haz) |