Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Miami |
---|---|
Assessment Year | 2007 |
Principal Product | Aircraft parts |
NAICS | 336413 - Other Aircraft Parts and Auxiliary Equipment Manufacturing |
SIC | 3728 - Aircraft Parts And Equipment, Nec |
Sales | $10,000,000-$50,000,000 |
# of Employees | 240 |
Plant Area (Sq.Ft.) | 277,000 |
Annual Production | 11,500 Pieces |
Production Hrs. Annual | 8,400 |
Location (State) | FL |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $448,522 | 6,506,400 | kWh | $0.07 |
Electricity Demand | $116,871 | 11,377 | kW-months/year | $10.27 |
Electricity Fees | $98,332 | - | $ | - |
TOTAL ENERGY COSTS | $663,725 | |||
RECOMMENDED SAVINGS* | $216,374 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $79,007 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Fees | Administrative Changes | Electricity Usage | Electricity Demand | Electricity Fees | Administrative Changes | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.2622 REPLACE EXISTING CHILLER WITH HIGH EFFICIENCY MODEL |
Savings: $99,787 Cost: $131,000 |
$82,492 | 1,178,460 | $17,295 | 1,684 | - | - | - | - |
$82,492 1,178,460 kWh |
$17,295 1,684 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $41,215 Cost: $73,710 |
$34,294 | 490,614 | - | - | $6,921 | - | - | - |
$34,294 490,614 kWh |
- - kW-months/year |
$6,921 - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7221 LOWER TEMPERATURE DURING THE WINTER SEASON AND VICE-VERSA |
Savings: $30,511 Cost: $120 |
$25,212 | 360,180 | $5,299 | 516 | - | - | - | - |
$25,212 360,180 kWh |
$5,299 516 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7122 DISCONNECT BALLASTS |
Savings: $27,192 Cost: $1,450 |
$18,319 | 262,080 | $8,873 | 864 | - | - | - | - |
$18,319 262,080 kWh |
$8,873 864 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.6231 UTILIZE CONTROLS TO OPERATE EQUIPMENT ONLY WHEN NEEDED |
Savings: $10,388 Cost: $1,250 |
$8,560 | 124,452 | $1,828 | 178 | - | - | - | - |
$8,560 124,452 kWh |
$1,828 178 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 4.821 PAY BILLS ON TIME TO AVOID LATE FEES |
Savings: $3,146 Cost: $300 |
- | - | - | - | - | - | $3,146 | - |
- - kWh |
- - kW-months/year |
- - $ |
$3,146 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $3,092 Cost: $1,074 |
$2,479 | 35,421 | $613 | 60 | - | - | - | - |
$2,479 35,421 kWh |
$613 60 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $1,043 Cost: $30 |
$796 | 11,365 | $247 | 24 | - | - | - | - |
$796 11,365 kWh |
$247 24 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $216,374 Cost: $208,934 |
$172,152 | 2,462,572 | $34,155 | 3,326 | $6,921 | - | $3,146 | - | $172,152 2,462,572 kWh |
$34,155 3,326 kW-months/year |
$6,921 - $ |
$3,146 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $79,007 Cost: $75,234 |
$62,781 | 897,580 | $6,159 | 600 | $6,921 | - | $3,146 | - | $62,781 897,580 kWh |
$6,159 600 kW-months/year |
$6,921 - $ |
$3,146 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Fees | Administrative Changes | Electricity Usage | Electricity Demand | Electricity Fees | Administrative Changes |