Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Miami |
---|---|
Assessment Year | 2007 |
Principal Product | Medical and Laboratory Rubber Sundries |
NAICS | 326299 - All Other Rubber Product Manufacturing |
SIC | 3069 - Fabricated Rubber Products, Nec |
Sales | $10,000,000-$50,000,000 |
# of Employees | 350 |
Plant Area (Sq.Ft.) | 125,000 |
Annual Production | 50,000,000 Pounds |
Production Hrs. Annual | 8,736 |
Location (State) | FL |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $1,047,150 | 13,922,476 | kWh | $0.08 |
Electricity Demand | $83,644 | 24,822 | kW-months/year | $3.37 |
Electricity Fees | $73,853 | - | $ | - |
Natural Gas | $527,254 | 452,950 | MMBtu | $1.16 |
TOTAL ENERGY COSTS | $1,731,901 | |||
RECOMMENDED SAVINGS* | $246,337 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $206,219 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Electricity Usage | Electricity Demand | Natural Gas | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7221 LOWER TEMPERATURE DURING THE WINTER SEASON AND VICE-VERSA |
Savings: $92,023 Cost: $8,580 |
$86,729 | 1,077,381 | $5,294 | 1,539 | - | - |
$86,729 1,077,381 kWh |
$5,294 1,539 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4322 USE OR REPLACE WITH ENERGY EFFICIENT SUBSTITUTES |
Savings: $55,437 Cost: $101,347 |
$45,097 | 560,166 | $10,340 | 235 | - | - |
$45,097 560,166 kWh |
$10,340 235 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7425 CLEAN OR COLOR ROOF TO REDUCE SOLAR LOAD |
Savings: $21,358 Cost: $46,238 |
$20,174 | 250,605 | $1,184 | 344 | - | - |
$20,174 250,605 kWh |
$1,184 344 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $21,963 Cost: $20,900 |
$20,745 | 257,712 | $1,218 | 354 | - | - |
$20,745 257,712 kWh |
$1,218 354 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $14,507 Cost: $1,210 |
$14,088 | 175,000 | $419 | 122 | - | - |
$14,088 175,000 kWh |
$419 122 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.2113 REPAIR OR REPLACE STEAM TRAPS |
Savings: $13,330 Cost: $1,700 |
- | - | - | - | $13,330 | 11,632 |
- - kWh |
- - kW-months/year |
$13,330 11,632 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $9,478 Cost: $5,967 |
$9,433 | 117,307 | $45 | 13 | - | - |
$9,433 117,307 kWh |
$45 13 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.4323 USE OPTIMUM SIZE AND CAPACITY EQUIPMENT |
Savings: $9,282 Cost: $3,475 |
$9,009 | 111,909 | $273 | 79 | - | - |
$9,009 111,909 kWh |
$273 79 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $5,073 Cost: $40 |
$4,732 | 58,778 | $341 | 100 | - | - |
$4,732 58,778 kWh |
$341 100 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.1233 ANALYZE FLUE GAS FOR PROPER AIR/FUEL RATIO |
Savings: $3,886 Cost: $2,000 |
- | - | - | - | $3,886 | 1,619 |
- - kWh |
- - kW-months/year |
$3,886 1,619 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $246,337 Cost: $191,457 |
$210,007 | 2,608,858 | $19,114 | 2,786 | $17,216 | 13,251 | $210,007 2,608,858 kWh |
$19,114 2,786 kW-months/year |
$17,216 13,251 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $206,219 Cost: $135,777 |
$171,391 | 2,129,037 | $17,612 | 2,350 | $17,216 | 13,251 | $171,391 2,129,037 kWh |
$17,612 2,350 kW-months/year |
$17,216 13,251 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Electricity Usage | Electricity Demand | Natural Gas |