Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Miami |
---|---|
Assessment Year | 2010 |
Principal Product | Newspapers |
NAICS | 511110 - Newspaper Publishers |
SIC | 2711 - Newspapers |
Sales | $10,000,000-$50,000,000 |
# of Employees | 200 |
Plant Area (Sq.Ft.) | 126,000 |
Annual Production | 35,000 Tons |
Production Hrs. Annual | 7,140 |
Location (State) | FL |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $564,160 | 7,881,343 | kWh | $0.07 |
Electricity Demand | $173,970 | 17,397 | kW-months/year | $10.00 |
Electricity Fees | $61,660 | - | $ | - |
TOTAL ENERGY COSTS | $799,790 | |||
RECOMMENDED SAVINGS* | $224,558 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $157,386 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Usage | Electricity Demand | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $60,080 Cost: $32,395 |
$52,700 | 526,996 | $7,380 | 738 |
$52,700 526,996 kWh |
$7,380 738 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7496 INSTALL PARTITIONS TO REDUCE SIZE OF CONDITIONED SPACE |
Savings: $39,832 Cost: $41,440 |
$34,102 | 252,534 | $5,730 | 573 |
$34,102 252,534 kWh |
$5,730 573 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7221 LOWER TEMPERATURE DURING THE WINTER SEASON AND VICE-VERSA |
Savings: $37,971 Cost: $1,020 |
$32,511 | 325,110 | $5,460 | 546 |
$32,511 325,110 kWh |
$5,460 546 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $21,844 Cost: $1,210 |
$18,704 | 187,039 | $3,140 | 314 |
$18,704 187,039 kWh |
$3,140 314 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.2628 UTILIZE A LESS EXPENSIVE COOLING METHOD |
Savings: $19,608 Cost: $35,500 |
$16,788 | 167,879 | $2,820 | 282 |
$16,788 167,879 kWh |
$2,820 282 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7221 LOWER TEMPERATURE DURING THE WINTER SEASON AND VICE-VERSA |
Savings: $17,417 Cost: $1,020 |
$14,907 | 149,071 | $2,510 | 251 |
$14,907 149,071 kWh |
$2,510 251 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $9,898 Cost: $40 |
$7,597 | 75,973 | $2,301 | 230 |
$7,597 75,973 kWh |
$2,301 230 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.4323 USE OPTIMUM SIZE AND CAPACITY EQUIPMENT |
Savings: $7,732 Cost: $4,531 |
$6,424 | 64,237 | $1,308 | 131 |
$6,424 64,237 kWh |
$1,308 131 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.7447 INSTALL VINYL STRIP / HIGH SPEED / AIR CURTAIN DOORS |
Savings: $10,176 Cost: $9,650 |
$8,716 | 87,160 | $1,460 | 146 |
$8,716 87,160 kWh |
$1,460 146 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $224,558 Cost: $126,806 |
$192,449 | 1,835,999 | $32,109 | 3,211 | $192,449 1,835,999 kWh |
$32,109 3,211 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $157,386 Cost: $45,335 |
$135,135 | 1,351,349 | $22,251 | 2,225 | $135,135 1,351,349 kWh |
$22,251 2,225 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Usage | Electricity Demand |