Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Miami |
---|---|
Assessment Year | 2011 |
Principal Product | Fruit Juice |
NAICS | 311411 - Frozen Fruit, Juice, and Vegetable Manufacturing |
SIC | 2037 - Frozen Fruits And Vegetables |
Sales | $100,000,000-$500,000,000 |
# of Employees | 740 |
Plant Area (Sq.Ft.) | 1,000,000 |
Annual Production | 80,000 Thousand Gallons |
Production Hrs. Annual | 8,568 |
Location (State) | FL |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $4,666,822 | 77,902,497 | kWh | $0.06 |
Electricity Demand | $173,576 | 134,837 | kW-months/year | $1.29 |
Natural Gas | $3,550,432 | 674,530 | MMBtu | $5.26 |
TOTAL ENERGY COSTS | $8,390,830 | |||
RECOMMENDED SAVINGS* | $258,520 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $83,606 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Electricity Usage | Electricity Demand | Natural Gas | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $64,568 Cost: $175,700 |
$62,955 | 912,388 | $1,613 | 1,253 | - | - |
$62,955 912,388 kWh |
$1,613 1,253 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7447 INSTALL VINYL STRIP / HIGH SPEED / AIR CURTAIN DOORS |
Savings: $39,559 Cost: $7,338 |
$38,190 | 553,480 | $1,369 | 1,064 | - | - |
$38,190 553,480 kWh |
$1,369 1,064 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $24,805 Cost: $1,320 |
$23,727 | 343,875 | $1,078 | 838 | - | - |
$23,727 343,875 kWh |
$1,078 838 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.1233 ANALYZE FLUE GAS FOR PROPER AIR/FUEL RATIO |
Savings: $20,342 Cost: $1,350 |
- | - | - | - | $20,342 | 3,860 |
- - kWh |
- - kW-months/year |
$20,342 3,860 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.2414 USE WASTE HEAT FROM HOT FLUE GASES TO PREHEAT |
Savings: $18,730 Cost: $26,000 |
- | - | - | - | $18,730 | 3,554 |
- - kWh |
- - kW-months/year |
$18,730 3,554 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7425 CLEAN OR COLOR ROOF TO REDUCE SOLAR LOAD |
Savings: $18,125 Cost: $133,000 |
$15,370 | 222,754 | $2,755 | 2,141 | - | - |
$15,370 222,754 kWh |
$2,755 2,141 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.6231 UTILIZE CONTROLS TO OPERATE EQUIPMENT ONLY WHEN NEEDED |
Savings: $17,851 Cost: $20,000 |
$17,406 | 252,312 | $445 | 346 | - | - |
$17,406 252,312 kWh |
$445 346 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.2136 INSTALL / REPAIR INSULATION ON STEAM LINES |
Savings: $16,463 Cost: $16,554 |
- | - | - | - | $16,463 | 3,124 |
- - kWh |
- - kW-months/year |
$16,463 3,124 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.2447 HEAT WATER WITH EXHAUST HEAT |
Savings: $16,131 Cost: $30,000 |
- | - | - | - | $16,131 | 3,061 |
- - kWh |
- - kW-months/year |
$16,131 3,061 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.7231 USE RADIANT HEATER FOR SPOT HEATING |
Savings: $8,346 Cost: $10,000 |
$8,138 | 117,936 | $208 | 162 | - | - |
$8,138 117,936 kWh |
$208 162 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
11: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $8,145 Cost: $8,889 |
$7,942 | 115,097 | $203 | 158 | - | - |
$7,942 115,097 kWh |
$203 158 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
12: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE |
Savings: $5,455 Cost: $2,425 |
$5,375 | 77,903 | $80 | 62 | - | - |
$5,375 77,903 kWh |
$80 62 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $258,520 Cost: $432,576 |
$179,103 | 2,595,745 | $7,751 | 6,024 | $71,666 | 13,599 | $179,103 2,595,745 kWh |
$7,751 6,024 kW-months/year |
$71,666 13,599 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $83,606 Cost: $181,634 |
$60,552 | 877,565 | $4,324 | 3,361 | $18,730 | 3,554 | $60,552 877,565 kWh |
$4,324 3,361 kW-months/year |
$18,730 3,554 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Electricity Usage | Electricity Demand | Natural Gas |