Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Miami |
---|---|
Assessment Year | 2014 |
Principal Product | Fruit Juice |
NAICS | 311411 - Frozen Fruit, Juice, and Vegetable Manufacturing |
SIC | 2037 - Frozen Fruits And Vegetables |
Sales | $10,000,000-$50,000,000 |
# of Employees | 85 |
Plant Area (Sq.Ft.) | 200,000 |
Annual Production | 1,500,000 Pieces |
Production Hrs. Annual | 5,616 |
Location (State) | FL |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $327,181 | 3,531,240 | kWh | $0.09 |
Electricity Demand | $93,198 | 12,897 | kW-months/year | $7.23 |
Electricity Fees | $24,189 | - | $ | - |
Natural Gas | $75,906 | 9,035 | MMBtu | $8.40 |
TOTAL ENERGY COSTS | $520,474 | |||
RECOMMENDED SAVINGS* | $71,008 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $20,319 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes | Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE |
Savings: $23,147 Cost: $3,600 |
$19,852 | 213,460 | $3,295 | 456 | - | - | - | - |
$19,852 213,460 kWh |
$3,295 456 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE |
Savings: $11,051 Cost: $500 |
$9,830 | 105,700 | $1,221 | 169 | - | - | - | - |
$9,830 105,700 kWh |
$1,221 169 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.2414 USE WASTE HEAT FROM HOT FLUE GASES TO PREHEAT |
Savings: $13,762 Cost: $28,000 |
- | - | - | - | $13,762 | 1,638 | - | - |
- - kWh |
- - kW-months/year |
$13,762 1,638 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.2447 HEAT WATER WITH EXHAUST HEAT |
Savings: $6,564 Cost: $8,859 |
- | - | - | - | $6,564 | 781 | - | - |
- - kWh |
- - kW-months/year |
$6,564 781 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.2614 USE COOLING TOWER OR ECONOMIZER TO REPLACE CHILLER COOLING |
Savings: $4,131 Cost: $4,980 |
$3,543 | 38,091 | $588 | 81 | - | - | - | - |
$3,543 38,091 kWh |
$588 81 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 3.4116 METER RECYCLED WATER (TO REDUCE SEWER CHARGES) |
Savings: $3,052 Cost: $560 |
- | - | - | - | - | - | $3,052 | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
$3,052 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $2,377 Cost: $10,770 |
$2,037 | 21,902 | $340 | 47 | - | - | - | - |
$2,037 21,902 kWh |
$340 47 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $1,643 Cost: $497 |
$1,412 | 15,181 | $231 | 32 | - | - | - | - |
$1,412 15,181 kWh |
$231 32 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $1,472 Cost: $1,660 |
$1,305 | 14,032 | $167 | 23 | - | - | - | - |
$1,305 14,032 kWh |
$167 23 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.2515 USE OPTIMUM THICKNESS INSULATION |
Savings: $1,375 Cost: $360 |
- | - | - | - | $1,375 | 163 | - | - |
- - kWh |
- - kW-months/year |
$1,375 163 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
11: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $1,317 Cost: $80 |
$1,120 | 12,047 | $197 | 27 | - | - | - | - |
$1,120 12,047 kWh |
$197 27 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
12: 2.2511 INSULATE BARE EQUIPMENT |
Savings: $708 Cost: $280 |
$607 | 6,526 | $101 | 14 | - | - | - | - |
$607 6,526 kWh |
$101 14 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
13: 2.7221 LOWER TEMPERATURE DURING THE WINTER SEASON AND VICE-VERSA |
Savings: $409 Cost: $173 |
$351 | 3,774 | $58 | 8 | - | - | - | - |
$351 3,774 kWh |
$58 8 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $71,008 Cost: $60,319 |
$40,057 | 430,713 | $6,198 | 857 | $21,701 | 2,582 | $3,052 | - | $40,057 430,713 kWh |
$6,198 857 kW-months/year |
$21,701 2,582 MMBtu |
$3,052 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $20,319 Cost: $3,830 |
$14,018 | 150,734 | $1,874 | 259 | $1,375 | 163 | $3,052 | - | $14,018 150,734 kWh |
$1,874 259 kW-months/year |
$1,375 163 MMBtu |
$3,052 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes | Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes |