Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Miami |
---|---|
Assessment Year | 2014 |
Principal Product | Boats |
NAICS | 336612 - Boat Building |
SIC | 3732 - Boat Building And Repairing |
Sales | $10,000,000-$50,000,000 |
# of Employees | 93 |
Plant Area (Sq.Ft.) | 40,000 |
Annual Production | 295 Pieces |
Production Hrs. Annual | 8,736 |
Location (State) | FL |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $43,606 | 675,793 | kWh | $0.06 |
Electricity Demand | $18,434 | 1,676 | kW-months/year | $11.00 |
Electricity Fees | $12,512 | - | $ | - |
Fuel Oil #2 | $7,814 | 302 | MMBtu | $25.86 |
Other Energy | $16,270 | 577 | MMBtu | $28.21 |
TOTAL ENERGY COSTS | $176,179 | |||
RECOMMENDED SAVINGS* | $54,908 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $34,196 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Other Energy | Other Liquid (haz) | Administrative Changes | Electricity Usage | Electricity Demand | Other Energy | Other Liquid (haz) | Administrative Changes | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | gal | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 3.8132 USE LESS TOXIC AND VOLATILE SOLVENT SUBSTITUTES |
Savings: $12,844 Cost: $14,320 |
- | - | - | - | - | - | $12,031 | 1,925 | $813 | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
$12,031 1,925 gal |
$813 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 3.5313 INCREASE AMOUNT OF WASTE RECOVERED FOR RESALE |
Savings: $8,400 Cost: $800 |
- | - | - | - | - | - | - | - | $8,400 | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
- - gal |
$8,400 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 3.8132 USE LESS TOXIC AND VOLATILE SOLVENT SUBSTITUTES |
Savings: $7,871 Cost: $640 |
- | - | - | - | - | - | - | - | $7,871 | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
- - gal |
$7,871 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT |
Savings: $7,868 Cost: $3,500 |
- | - | - | - | $7,868 | 272 | - | - | - | - |
- - kWh |
- - kW-months/year |
$7,868 272 MMBtu |
- - gal |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7145 INSTALL SKYLIGHTS |
Savings: $5,746 Cost: $630 |
$4,656 | 72,159 | $1,090 | 99 | - | - | - | - | - | - |
$4,656 72,159 kWh |
$1,090 99 kW-months/year |
- - MMBtu |
- - gal |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $4,486 Cost: $1,310 |
$3,639 | 55,990 | $847 | 77 | - | - | - | - | - | - |
$3,639 55,990 kWh |
$847 77 kW-months/year |
- - MMBtu |
- - gal |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $3,344 Cost: $9,120 |
$2,706 | 41,933 | $638 | 58 | - | - | - | - | - | - |
$2,706 41,933 kWh |
$638 58 kW-months/year |
- - MMBtu |
- - gal |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $2,899 Cost: $80 |
$2,349 | 36,142 | $550 | 50 | - | - | - | - | - | - |
$2,349 36,142 kWh |
$550 50 kW-months/year |
- - MMBtu |
- - gal |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.7134 USE PHOTOCELL CONTROLS |
Savings: $1,450 Cost: $360 |
$988 | 15,200 | $462 | 42 | - | - | - | - | - | - |
$988 15,200 kWh |
$462 42 kW-months/year |
- - MMBtu |
- - gal |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $54,908 Cost: $30,760 |
$14,338 | 221,424 | $3,587 | 326 | $7,868 | 272 | $12,031 | 1,925 | $17,084 | - | $14,338 221,424 kWh |
$3,587 326 kW-months/year |
$7,868 272 MMBtu |
$12,031 1,925 gal |
$17,084 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $34,196 Cost: $12,940 |
$14,338 | 221,424 | $3,587 | 326 | - | - | - | - | $16,271 | - | $14,338 221,424 kWh |
$3,587 326 kW-months/year |
- - MMBtu |
- - gal |
$16,271 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | gal | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Other Energy | Other Liquid (haz) | Administrative Changes | Electricity Usage | Electricity Demand | Other Energy | Other Liquid (haz) | Administrative Changes |