Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of Miami
Assessment Year 2017
Principal Product plastic cups
NAICS 326199 - All Other Plastics Product Manufacturing
SIC 3089 - Plastics Products, Nec
Sales $100,000,000-$500,000,000
# of Employees 500
Plant Area (Sq.Ft.) 113,000
Annual Production 16,000,000 Units
Production Hrs. Annual 4,160
Location (State) FL
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $133,972 2,754,180 kWh $0.05
Electricity Demand $63,062 6,066 kW-months/year $10.40
Electricity Fees $44,365 - $ -
TOTAL ENERGY COSTS $241,399
RECOMMENDED SAVINGS* $101,511 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $16,869
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Administrative Changes Electricity Usage Electricity Demand Administrative Changes
$ kWh $ kW-months/year $ $
01: 2.3113 MAKE ICE DURING OFF PEAK HOURS FOR COOLING Savings:
$53,389
Cost:
$312,800
- - $37,467 3,604 $15,922 - -
-
kWh
$37,467
3,604
kW-months/year
$15,922
-
$
02: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$13,953
Cost:
$33,615
$7,102 144,947 $6,851 659 - - $7,102
144,947
kWh
$6,851
659
kW-months/year
-
-
$
03: 2.7221 LOWER TEMPERATURE DURING THE WINTER SEASON AND VICE-VERSA Savings:
$7,316
Cost:
$240
$7,316 149,300 - - - - $7,316
149,300
kWh
-
-
kW-months/year
-
-
$
04: 2.7447 INSTALL VINYL STRIP / HIGH SPEED / AIR CURTAIN DOORS Savings:
$4,609
Cost:
$8,095
$3,413 69,643 $1,196 115 - - $3,413
69,643
kWh
$1,196
115
kW-months/year
-
-
$
05: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$4,512
Cost:
$14,280
$4,512 92,077 - - - - $4,512
92,077
kWh
-
-
kW-months/year
-
-
$
06: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT Savings:
$4,286
Cost:
$9,500
$4,286 87,486 - - - - $4,286
87,486
kWh
-
-
kW-months/year
-
-
$
07: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$4,134
Cost:
$1,660
$1,711 34,922 $2,423 233 - - $1,711
34,922
kWh
$2,423
233
kW-months/year
-
-
$
08: 2.7496 INSTALL PARTITIONS TO REDUCE SIZE OF CONDITIONED SPACE Savings:
$3,893
Cost:
$8,040
$2,417 49,325 $1,476 142 - - $2,417
49,325
kWh
$1,476
142
kW-months/year
-
-
$
09: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS Savings:
$2,238
Cost:
$650
$1,573 32,099 $665 64 - - $1,573
32,099
kWh
$665
64
kW-months/year
-
-
$
10: 2.7135 INSTALL OCCUPANCY SENSORS Savings:
$1,858
Cost:
$177
$1,858 37,923 - - - - $1,858
37,923
kWh
-
-
kW-months/year
-
-
$
11: 2.7221 LOWER TEMPERATURE DURING THE WINTER SEASON AND VICE-VERSA Savings:
$711
Cost:
$120
$711 14,500 - - - - $711
14,500
kWh
-
-
kW-months/year
-
-
$
12: 2.7135 INSTALL OCCUPANCY SENSORS Savings:
$612
Cost:
$1,630
$612 12,496 - - - - $612
12,496
kWh
-
-
kW-months/year
-
-
$
TOTAL RECOMMENDED Savings:
$101,511
Cost:
$390,807
$35,511 724,718 $50,078 4,817 $15,922 - $35,511
724,718
kWh
$50,078
4,817
kW-months/year
$15,922
-
$
TOTAL IMPLEMENTED Savings:
$16,869
Cost:
$4,477
$13,781 281,240 $3,088 297 - - $13,781
281,240
kWh
$3,088
297
kW-months/year
-
-
$
Savings
Cost
$ kWh $ kW-months/year $ $
Electricity Usage Electricity Demand Administrative Changes Electricity Usage Electricity Demand Administrative Changes