Select a Center

Arizona State University
Boise State University
Case Western Reserve University
Clemson University
Colorado State University
Georgia Institute of Technology
Indiana University-Purdue University
Lehigh University
Louisiana State University
North Carolina State
Oklahoma State University
Oregon State University
San Diego State University
San Francisco State University
Syracuse University
Tennessee Technological University
Texas A&M, College Station
University of Alabama
University of Dayton
University of Delaware
University of Florida
University of Illinois, Chicago
University of Kentucky
University of Massachusetts
University of Miami
University of Missouri-Columbia
University of Nebraska–Lincoln
University of Texas Rio Grande Valley
University of Utah
University of Wisconsin, Milwaukee
West Virginia University
IAC logo
IAC Assessment: MI0321
Sponsored by:
EERE AMO
IAC logo
IAC Assessment: MI0321
IAC Center University of Miami
Assessment Year 2017
Principal Product Electric Coils and Valves
NAICS 334416 - Capacitor, Resistor, Coil, Transformer, and Other Inductor Manufacturing
SIC 3677 - Electronic Coils And Transformers
Sales $2,270,000
# of Employees 50
Plant Area (Sq.Ft.) 23,500
Annual Production 961,000 Pieces
Production Hrs. Annual 2,210
Location (State) PR
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $79,042 456,280 kWh $0.17
Electricity Demand $23,927 2,512 kW-months/year $9.53
Electricity Fees $2,626 - $ -
TOTAL ENERGY COSTS $105,596
RECOMMENDED SAVINGS* $58,893 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $40,636
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Electricity Fees Electricity Usage Electricity Demand Electricity Fees
$ kWh $ kW-months/year $ $
01: 2.2515 USE OPTIMUM THICKNESS INSULATION Savings:
$17,954
Cost:
$21,920
$13,821 79,891 $4,133 434 - - $13,821
79,891
kWh
$4,133
434
kW-months/year
-
-
$
02: 2.7425 CLEAN OR COLOR ROOF TO REDUCE SOLAR LOAD Savings:
$10,816
Cost:
$7,589
$8,552 49,435 $2,264 238 - - $8,552
49,435
kWh
$2,264
238
kW-months/year
-
-
$
03: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE Savings:
$7,233
Cost:
$3,600
$7,233 41,808 - - - - $7,233
41,808
kWh
-
-
kW-months/year
-
-
$
04: 2.4322 USE OR REPLACE WITH ENERGY EFFICIENT SUBSTITUTES Savings:
$6,777
Cost:
$5,492
$5,217 30,157 $1,560 164 - - $5,217
30,157
kWh
$1,560
164
kW-months/year
-
-
$
05: 2.8114 CHANGE RATE SCHEDULES OR OTHER CHANGES IN UTILITY SERVICE Savings:
$5,988
Cost:
$6,400
- - - - $5,988 - -
-
kWh
-
-
kW-months/year
$5,988
-
$
06: 2.3212 OPTIMIZE PLANT POWER FACTOR Savings:
$3,370
Cost:
$10,745
- - $3,370 354 - - -
-
kWh
$3,370
354
kW-months/year
-
-
$
07: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$2,256
Cost:
$1,660
$1,408 8,139 $848 89 - - $1,408
8,139
kWh
$848
89
kW-months/year
-
-
$
08: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM Savings:
$2,121
Cost:
$1,508
$1,972 11,400 $149 16 - - $1,972
11,400
kWh
$149
16
kW-months/year
-
-
$
09: 2.2511 INSULATE BARE EQUIPMENT Savings:
$1,612
Cost:
$1,914
$1,298 5,694 $313 33 - - $1,298
5,694
kWh
$313
33
kW-months/year
-
-
$
10: 2.7221 LOWER TEMPERATURE DURING THE WINTER SEASON AND VICE-VERSA Savings:
$766
Cost:
$400
$590 3,409 $176 19 - - $590
3,409
kWh
$176
19
kW-months/year
-
-
$
TOTAL RECOMMENDED Savings:
$58,893
Cost:
$61,228
$40,092 229,933 $12,813 1,346 $5,988 - $40,092
229,933
kWh
$12,813
1,346
kW-months/year
$5,988
-
$
TOTAL IMPLEMENTED Savings:
$40,636
Cost:
$37,083
$32,903 188,376 $7,734 812 - - $32,903
188,376
kWh
$7,734
812
kW-months/year
-
-
$
Savings
Cost
$ kWh $ kW-months/year $ $
Electricity Usage Electricity Demand Electricity Fees Electricity Usage Electricity Demand Electricity Fees